Step 2
Complete the
to discontinue alarm suppression and resume
normal alarm reporting.
Stop. You have completed this procedure.
DLP-G129 Suppress Alarm Reporting
This task suppresses the reporting of ONS 15454 alarms at the node, shelf, card, or
port level.
Purpose
None
Tools/Equipment
"DLP-G46 Log into CTC" task in the "
document.
Prerequisite Procedures
As needed
Required/As Needed
Onsite or remote
Onsite/Remote
Provisioning or higher
Security Level
If multiple CTC/TL1 sessions are open, suppressing alarms in one session suppresses the alarms in all
other open sessions.
Caution
Alarm suppression at the node level does not supersede alarm suppression at the card or port level.
Suppression can exist independently for all three entities, and each entity will raise separate alarms
suppressed by the user command (AS-CMD) alarm.
Note
Procedure
Step 1
From the network view, right-click the node you want to suppress alarms and choose Open Node. From node view, click
the Provisioning > Alarm Profiles > Alarm Behavior tabs.
Step 2
To suppress alarms for the entire node:
a) Check the Suppress Alarms check box.
b) Click Apply.
All raised alarms for the node will change color to white in the Alarms window and their status will change to cleared.
After suppressing alarms, clicking Synchronize in the Alarms window will remove cleared alarms from the window.
However, an AS-CMD alarm will show in node or card view to indicate that node-level alarms were suppressed, and
the word System will appear in the Object column.
The only way to suppress building integrated timing supply (BITS), power source, or system alarms is to
suppress alarms for all the non-card objects.
Note