Power Supply  :  230V Single Phase 60Hz
 RATING CAPACITY:    24,800 BTU/h
      AIR FLOW RATE:
812 CFM
INDOOR
OUTDOOR
 ENT. TEMP. 
o
F (
o
C)
    AMBIENT TEMP. 
o
F (
o
C)
WB
DB
15
25
35
45
55
(-9.4)
(-3.9)
(1.7)
(7.2)
(12.8)
TC
24,890
24,830
24,880
25,090
25,020
72 (22.2)
SHC
19,360
24,830
19,360
19,520
19,520
59
76 (24.4)
SHC
22,200
24,830
22,200
22,200
22,200
(15.0)
80 (26.7)
SHC
24,890
24,830
24,880
25,090
25,020
84 (28.9)
SHC
24,890
24,830
24,880
25,090
25,020
88 (31.1)
SHC
24,890
24,830
24,880
25,090
25,020
TC
25,020
25,050
25,250
25,620
25,660
72 (22.2)
SHC
15,730
25,050
15,890
16,050
16,050
63
76 (24.4)
SHC
18,570
25,050
18,570
18,730
18,890
(17.2)
80 (26.7)
SHC
21,410
25,050
21,570
21,730
21,730
84 (28.9)
SHC
24,250
25,050
24,250
24,410
24,570
88 (31.1)
SHC
25,020
25,050
25,250
25,620
25,660
TC
24,930
25,080
25,450
26,030
26,200
72 (22.2)
SHC
12,100
25,080
12,260
12,420
12,580
67
76 (24.4)
SHC
14,790
25,080
15,100
15,260
15,420
(19.4)
80 (26.7)
SHC
17,780
25,080
17,940
18,260
18,260
84 (28.9)
SHC
20,460
25,080
20,780
20,940
21,100
88 (31.1)
SHC
23,300
25,080
23,460
23,780
23,780
TC
24,560
24,850
25,440
26,280
26,600
72 (22.2)
SHC
8,160
24,850
8,480
8,790
8,950
71
76 (24.4)
SHC
11,000
24,850
11,320
11,630
11,630
(21.7)
80 (26.7)
SHC
13,840
24,850
14,160
14,470
14,630
84 (28.9)
SHC
16,680
24,850
16,990
17,310
17,310
88 (31.1)
SHC
19,360
24,850
19,680
19,990
20,150
TC
23,930
24,370
25,200
26,320
26,810
75
76 (24.4)
SHC
7,220
24,370
7,690
8,000
8,160
(23.9)
80 (26.7)
SHC
10,050
24,370
10,530
10,840
11,000
84 (28.9)
SHC
12,890
24,370
13,370
13,680
13,840
88 (31.1)
SHC
15,730
24,370
16,050
16,520
16,680
NOTE
< Cooling Capacity (Low Ambient) >
TC : Total Cooling Capacity (BTU/h)   SHC : Sensible Heat Capacity (BTU/h)
1.
2. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Freeze Prevention Protection during cooling operation into account. 
For this reason, the value may vary from the actual cooling characteristics.