Schneider Electric MGE Galaxy 5000 User Manual
static switch, battery plant, graphical status/control panel, dry contact and communications
ports, and synchronizing circuitry as described herein.
ports, and synchronizing circuitry as described herein.
2.2 SYSTEM
DESCRIPTION
A. UPS Design Requirements
1. Output Power Continuous Rating: The continuous output power rating of the UPS shall
be [ ] kVA at a 0.9 lagging power factor.
Galaxy 5000 available: Choose 40, 50, 60, 80, 100, 130kVA
2. Input Voltage: 480 VAC – 15% / +10%, 3 phase, 3 wire “grounded wye” configuration
plus ground.
3. Output voltage: 480 VAC 3 phase, 3 plus ground
4. Battery Autonomy: The UPS shall be capable of operating at full load for [ ] minutes at
0.9 PF output at a temperature of 25°C on battery power.
5. Battery Type: Valve regulated sealed lead acid (VRLA)
B. AC Input Characteristics
1. Voltage: 480VAC, – 15% / +10%, 3 phase, 3 wire “grounded wye” configuration plus
ground.
2. Frequency: 60 Hz ±5%
3. Power Factor: > .98 lagging
4. Total Harmonic Distortion: less than 5% at full load
5. Inrush Current: less than nominal input current for less than one cycle
6. Input Surge Protection: The UPS is equipped to withstand surges per IEC 1004/ANSI
3. Power Factor: > .98 lagging
4. Total Harmonic Distortion: less than 5% at full load
5. Inrush Current: less than nominal input current for less than one cycle
6. Input Surge Protection: The UPS is equipped to withstand surges per IEC 1004/ANSI
C62.41
C. AC Output Characteristics
1. Voltage: 480VAC , – /+ 1% steady-state variation phase to phase voltage VAC , 3 phase,
3 wire plus ground
2. Frequency: 60 Hz +1% (or selectable up to 4%); 60 Hz + 0.1% when free running
3. Voltage Regulation:
3. Voltage Regulation:
+ 1.0% for balanced load
+ 1.75 for 50% unbalanced load
+ 2.5% for 100% unbalanced load
+ 1.75 for 50% unbalanced load
+ 2.5% for 100% unbalanced load
4. Voltage
Distortion: Maximum 2% total (THD) and 1% any single harmonic on 100% linear
loads.
5. Voltage Transient (Step Load) Response: + 3% for 50% step load change
+ 5% for 100% step load change
APC – MGE Galaxy 5000 Specification (60Hz)
4
Effective: June 1, 2008 REV X0 JJG
Parallel Module