Schneider Electric MGE Galaxy 5000 User Manual

Page of 17
 
+ 1% for loss or return of AC input power or  
 
manual transfer at full load 
 
 
6. Voltage 
Recovery 
Time:  Return to within 1% of nominal value within 16.67 milliseconds 
(one cycle) 
 
7.  Phase Angle Displacement 120° + 1° for balanced load; 120° + 3° for 100% unbalanced 
load 
 
8.  Non-Linear Load Capability: Output voltage total harmonic distortion shall be less than 
3% when connected to a 100% non-linear load with a crest factor not to exceed 3%. 
 
9.  Slew Rate:  1 Hz/second maximum (or selectable up to 2.0 Hz/sec) 
 
10.  Power Factor:  0.9 at the rated volt-amperes (VA) 
 
11.  Inverter Overload Capability:    125% of rated load for 10 minutes  
 
 
 
 
 
150% of rated load for 1 minute 
 
 
 
 
 
 
 
 
 
12.  Bypass Overload Capability:  > 212% for one cycle; > 150% for 1 minute 
 
 
D.  Battery 
 
1.  Battery Voltage: 356 VDC minimum before cutoff; 432 VDC nominal; 490 VDC 
equalization voltage 
 
2.  Maximum DC Current:  Maximum DC current at cutoff voltage will be [        ] A. 
 
2.3
 
MODES OF OPERATION
 
 
The UPS module shall be designed to operate as a double conversion, on-line reverse transfer 
system in the following modes. 
 
A.  Normal: The inverter shall continuously supply power to the critical load.  The PFC rectifier shall 
derive power from the utility AC source and supply DC power to the inverter while 
simultaneously float charging the battery. 
 
B.  Emergency:  Upon failure of the utility AC power source, the critical load shall be supplied by 
the inverter, which, without any interruption, shall obtain its power from the battery. 
 
C.  Recharge: Upon restoration of the utility AC power source (prior to complete battery discharge), 
the PFC rectifier shall power the inverter and simultaneously recharge the battery. 
 
D.  Bypass Mode: The static bypass transfer switch shall be used to transfer the load to the 
bypass without interruption to the critical power load.  This shall be accomplished by turning the 
inverter off.  Automatic re-transfer or forward transfer of the load shall be accomplished by 
turning the inverter on. 
 
 
2.4 COMPONENT 
DESCRIPTION 
 
A.  PFC Rectifier and Battery Charger 
 
 
APC – MGE Galaxy 5000 Specification  (60Hz) 
5
 
Effective:  June 1, 2008 REV X0 JJG 
Parallel Module