ELECTRICAL REQUIREMENTS - U.S.A. ONLY
It is your responsibility
To contact a qualified electrical installer.
To be sure that the electrical connection is adequate and in conformance with the 
National Electrical Code, ANSI/NFPA 70-latest edition and all local codes and 
ordinances. 
The National Electric Code requires a 4-wire power supply connection for homes built 
after 1996, dryer circuits involved in remodeling after 1996, and all mobile home 
installations.
A copy of the above code standards can be obtained from: National Fire Protection 
Association, One Batterymarch Park, Quincy, MA 02269.
To supply the required 3 or 4 wire, single phase, 120/240volt, 60Hz., AC only electrical 
supply (or 3 or 4 wire, 120/208 volt electrical supply, if specified on the serial/rating plate) 
on a separate 30-amp circuit, fused on both sides of the line. A time-delay fuse or circuit 
breaker is recommended. Connect to an individual branch circuit. Do not have a fuse in 
the neutral or grounding circuit. 
Do not use an extension cord.
If codes permit and a separate ground wire is used, it is recommended that a qualified 
electrician determine that the ground path is adequate.
Electrical Connection
To properly install your dryer, you must determine the type of electrical connection you will 
be using and follow the instructions provided for it here.
This dryer is manufactured ready to install with a 3-wire electrical supply connection. The 
neutral ground conductor is permanently connected to the neutral conductor (white wire) 
within the dryer. If the dryer is installed with a 4-wire electrical supply connection, the 
neutral ground conductor must be removed from the external ground connector (green 
screw), and secured under the neutral terminal (center or white wire) of the terminal 
block. When the neutral ground conductor is secured under the neutral terminal (center 
or white wire) of the terminal block, the dryer cabinet is isolated from the neutral 
conductor.
If local codes do not permit the connection of a neutral ground wire to the neutral wire, 
see “Optional 3-wire connection” in “Electrical Connection - U.S.A. Only” section. 
A 4-wire power supply connection must be used when the appliance is installed in a 
location where grounding through the neutral conductor is prohibited. Grounding 
through the neutral is prohibited for (1) new branch-circuit installations, (2) mobile 
homes, (3) recreational vehicles, and (4) areas where local codes prohibit grounding 
through the neutral conductors.
If using a power supply cord:
Use a UL listed power supply cord kit marked for use with clothes dryers. The kit should 
contain:
A UL listed 30-amp power supply cord, rated 120/240 volt minimum. The cord should be 
type SRD or SRDT and be at least 4 ft (1.22 m) long. The wires that connect to the dryer 
must end in ring terminals or spade terminals with upturned ends.
A UL listed strain relief.
If your outlet looks like this:
4-wire receptacle (14-30R)
Then choose a 4-wire power supply cord with ring or spade terminals and UL listed strain 
relief. The 4-wire power supply cord, at least 4 ft (1.22 m) long, must have four 10-gauge 
copper wires and match a 4-wire receptacle of NEMA Type 14-30R. The ground wire (ground 
conductor) may be either green or bare. The neutral conductor must be identified by a white 
cover.
If your outlet looks like this:
3-wire receptacle (10-30R)
Then choose a 3-wire power supply cord with ring or spade terminals and UL listed strain 
relief. The 3-wire power supply cord, at least 4 ft (1.22 m) long, must have three 10-gauge 
copper wires and match a 3-wire receptacle of NEMA Type 10-30R.
If connecting by direct wire:
Power supply cable must match power supply (4-wire or 3-wire) and be:
Flexible armored cable or nonmetallic sheathed copper cable (with ground wire), 
protected with flexible metallic conduit. All current-carrying wires must be insulated.  
10-gauge solid copper wire (do not use aluminum).
At least 5 ft (1.52 m) long.