heatcraft-refrigeration-p h-im-fl1a User Manual

Page of 24
13
NOTE: All adjustable controls and valves must be field 
adjusted to meet desired operation. There are no 
factory preset controls or valve adjustments.
System Balancing - Compressor Superheat 
 
   
IMPORTANT:  In order to obtain the maximum capacity     
                             from a system, and to ensure trouble- 
                             free operation, it is necessary to balance  
                             each and every system.
This is extremely important with any refrigeration system.
The critical value which must be checked is suction superheat.
Suction superheat should be checked at the compressor  
as follows: 
 
 
1.  Measure the suction pressure at the suction service  
 
 
valve of the compressor and determine the saturation 
  
 
temperature corresponding to this pressure from a  
 
 
“Temperature-Pressure” chart. 
 
 
2.  Measure the suction temperature of the suction line 
  
 
about one foot back from the compressor using an    
 
 
 accurate thermometer. 
 
 
3.  Subtract the saturated temperature from the actual  
 
 
suction line temperature. The difference is superheat.
Too low a suction superheat can result in liquid being returned 
to the compressor. This will cause dilution of the oil and 
eventual failure of the bearings and rings or in the extreme 
case, valve failure.
Too high a suction superheat will result in excessive discharge 
temperatures which cause a break down of the oil and results 
in piston ring wear, piston and cylinder wall damage. 
It should also be remembered that the system capacity 
decreases as the suction superheat increases. For maximum 
system capacity, suction superheat should be kept as low as 
is practical. Copeland mandates a minimum superheat of 
20˚F at the compressorHeatcraft Refrigeration Products 
recommends that the superheat at the compressor be 
between 30˚F and 45˚F.
If adjustments to the suction superheat need to be made,  
the expansion valve at the evaporator should be adjusted.
Operational Check Out 
 
After the system has been charged and has operated for at 
least two hours at normal operating conditions without any 
indication of malfunction, it should be allowed to operate 
overnight on automatic controls. Then a thorough recheck of the 
entire system operation should be made as follows: 
 
(a)  Check compressor discharge and suction pressures. 
    
If not within system design limits, determine why and 
 
 
 take corrective action. 
 
(b)  Check liquid line sight glass and expansion valve  
 
 
operation. If there are indications that more refrigerant  
 
 
is required, leak test all connections and system  
 
 
components and repair any leaks before adding  
 
 
refrigerant.  
 
(c)  Thermostatic expansion valves must be checked for  
 
 
proper superheat settings. Feeler bulbs must be in 
 
 
positive contact with the suction line and should be  
 
 
insulated. Valves set at high superheat will lower  
 
 
refrigeration capacity. Low superheat promotes liquid  
 
 
slugging and compressor bearing washout. 
 
(d)  Using suitable instruments, carefully check line voltage  
 
 
and amperage at the compressor terminals. Voltage  
 
 
must be within 10% of that indicated on the    
 
 
 
condensing unit nameplate. If high or low voltage is    
 
 
indicated, notify the power company. If amperage draw  
 
 
is excessive, immediately determine the cause and  
 
 
take corrective action. On three phase motor   
 
 
compressors, check to see that a balanced load is  
 
 
 
drawn by each phase.  
 
(e)  The maximum approved settings for high pressure  
 
 
controls on Heatcraft air cooled condensing equipment  
 
 
is 400 psig. On air cooled systems, check as follows:    
 
 
Disconnect the fan motors or block the condenser  
 
 
inlet air. Watch high pressure gauge for cutout point.   
 
 
Recheck all safety and operating controls for proper    
 
 
operation and adjust if necessary.  
 
(f)  Check winter head pressure controls for pressure  
 
 
setting.
 
(g)  Check crankcase heater operation if used. 
 
(h)  Install instruction card and control system diagram for   
 
 
use of building manager or owner.