Fagor nc-200 pb Installation Instruction

Page of 58
 NC-200 PB  -  Installation Manual - Page: 47
PAR64
Press brake model definition
digit
8
Not being used at this time. It must be set to "0".
7
If = 0, pin 18 of connector X2 is selected as the analog input for the
PRESSURE/VOLTAGE gage or potentiometric scale.
Both options are incompatible.
This operation requires a position change at the selector installed in
the circuit of connector X2 which is accessed by removing the rear
board: To set pin 18 as analog input, put the jumper towards "U4".
Set PAR46.5 and PAR46.3 to "0" to configure the X axis in open
loop.
If = 1 and jumper towards "U7", it is set as an analog output.
6
Setting of pin 18
If = 0, it is selected as analog output for the X axis.
If = 1, it is selected as an input or output (PAR64.7) for the pressure
gage.
The X axis will be controlled in open loop without using the analog
output PAR46.5 = 0, PAR46.3 = 0.
2
If =0, LCD screen
If =1, VFD screen (blue)
1
Not being used at this time. It must be set to "0".
5
4
3
Press brake 
model
Description
0
0
0
A
Only the final bend position is controlled
1
0
0
A1
Same as model A with footswitch handling
0
1
0
B
Same as model A1 with linear encoder for 
decoded intermediate ram-bed positions
0
0
1
C
Control of actual ram-bed position with footswitch 
and "busy hands" handling.