8 Connection of External Signals
8.4 All-Unit Alarm Output
An external signal is output when an alarm or error occurs in any connected unit.
This signal can be used by alarm monitors and other equipment.
1) Output location
The communications connector panel on the side of the Intelligent Controller or on an optional 
communication adaptor connected to the Intelligent Controller:
 
DO1 (No.14), DO-COMM (No.13)
2) Operation
The signal goes ON when an alarm or error occurs, and goes OFF when normal status is 
restored.
8.5 All-Unit Operation Output
An external signal is output when any connected unit is operating.
1) Output location
The communications connector panel on the side of the Intelligent Controller or on an optional 
communication adaptor connected to the Intelligent Controller:
 
DO2 (No.15), DO-COMM (No.13)
2) Operation
The signal goes ON when any connected unit (including Interface adaptor) is operating, and 
goes OFF when all units are stopped.
Operation during alarms and errors is included.