Puls ML50.100 Power Supply Guia De Especificação

Página de 20
 
 
 
ML50.100, ML50.109 
 
MiniLine 
 
24V, 2.1A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
Mar. 2007 / Rev. 1.0  DS-ML50.100-EN 
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
11/20 
 
17. E
NVIRONMENT
 
 
  Operational temperature 
-10°C to +70°C (14°F to 158°F) 
Reduce output power according to 
Fig. 17-1
 
  Output de-rating 
1.3W/°C 
60-70°C   (140°F to 158°F), see 
Fig. 17-1
 
  Storage temperature 
-40 to +85°C  (-40°F to 185°F) 
Storage and transportation 
 
Humidity 
5 to 95% r.H. 
IEC 60068-2-30  
Do not energize while condensation is present
 
 
Vibration sinusoidal 
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g 
2 hours / axis 
IEC 60068-2-6 
 
Shock 
20g 6ms, 10g 11ms 
3 bumps / direction, 18 bumps in total 
IEC 60068-2-27 
  Altitude 
0 to 6000m  (0 to 20000ft) 
Reduce output power or ambient 
temperature above 2000m sea level. 
  Output de-rating (for altitude) 
3W/1000m or 5°C/1000m 
Above 2000m (6500ft), see 
Fig. 17-2
 
  Over-voltage category 
III 
EN 50178, IEC 62103 altitudes < 2000m  
   
II 
Altitudes from 2000m to 6000m 
  Degree of pollution 
EN 50178, IEC 62103, non conductive 
 
 
Fig. 17-1   Output current vs. ambient temp. 
 
Fig. 17-2   Output current vs. altitude, 24V 
 
0
-10
0
20
40
70°C
0.4
0.8
1.2
1.6
2.0
2.4A
60
Ambient Temperature
Allowable Output
Current at 24V
 
 
0
0
2000
4000
6000m
0.4
0.8
1.2
1.6
2.0
2.4A
Altitude
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
A
B
C
Allowable Output
Current at 24V
 
The ambient temperature is defined 2cm below the unit. 
 
 
18. P
ROTECTION 
F
EATURES
 
 
 Output 
protection 
Electronically protected against overload, no-load and short-circuits 
  Output over-voltage protection 
typ. 36V 
max. 39V 
In case of an internal power supply fault, a redundant 
circuit limits the maximum output voltage. The output 
shuts down and automatically attempts to restart. 
  Output over-current protection electronically 
limited see 
Fig. 10-1
 
  Degree of protection 
IP 20 
EN/IEC 60529 
  Penetration protection 
> 2.5mm in diameter 
E.g. screws, small parts 
  Over-temperature protection 
not included 
 
  Input transient protection 
MOV  
Metal Oxide Varistor 
 Internal 
input 
fuse 
T3.15A H.B.C. 
Not user replaceable 
Note: In case of a over-voltage, overload, no-load or short-circuit event, an audible noise may be heard.