Nortel 8005 AC POWER SUPPLY 100V/240V 1140W/1462W Specification Guide
40 Chapter 2 Installing power supplies
312751-E Rev 01
You can remove a redundant power supply without affecting the operation of the
8600 Series switch. When you remove a power supply, the LED on the power
supply turns off, and the 8600 Series chassis automatically redistributes the load
to the remaining power supplies.
8600 Series switch. When you remove a power supply, the LED on the power
supply turns off, and the 8600 Series chassis automatically redistributes the load
to the remaining power supplies.
You should replace a failed power supply as soon as possible to restore
high-availability operation.
high-availability operation.
To remove an AC power supply:
1
If you are removing a power supply from a 8010co chassis, remove the
bottom front bezel.
bottom front bezel.
For instructions, see
” on page
2
Turn off the power switch on the power supply that you are replacing
(
(
).
Figure 22 AC power supply power switch off: 8010co chassis
Caution: To maintain proper cooling, never operate the 8600 Series
chassis with an empty power supply bay. If you are replacing a failed
power supply and you do not have a power filler panel, leave the failed
power supply installed until a replacement power supply is available.
chassis with an empty power supply bay. If you are replacing a failed
power supply and you do not have a power filler panel, leave the failed
power supply installed until a replacement power supply is available.
10342FA