Chapter 4 Removal and Replacement Procedures
Removing and Installing the DC-Input Power Supplies
Figure 4-22 DC-Input Front Panel for 2700-W DC-Input Power Supply
Warning
Power supply captive installation screws must be tight to ensure protective grounding continuity.
Statement 289
Statement 289
Step 5
Remove the four screws securing the terminal block cover, and slide the cover off of the terminal block.
(See
(See
.)
Step 6
Attach the appropriate lugs to the DC-input wires. The maximum width of a lug is 0.300 inch (7.6 mm).
The wire should be sized according to local and national installation requirements. Use only copper wire.
The wire should be sized according to local and national installation requirements. Use only copper wire.
Note
For 2700 W power supplies, use fine-stranded copper conductors that are rated for 90-degrees
Celsius for North American installations.
Celsius for North American installations.
1
Captive installation screw
7
Cable holder cover
2
DC power cable terminal block
8
Cable holder
3
Status LEDs
9
Tie-wrap
4
DC power cable terminal block cover
10 Cable holder
5
Cable holder cover
11 Tie-wrap
6
Ground terminal block
132219
PWR-2700-DC/4
-VE-1
-VE-1
-VE-2
-VE-2
INPUT1
OK
48V-60V
=40A
INPUT2
OK
48V-60V
=40A
FAN
OK
OUTPUT
FAIL
ALL F
ASTENERS MUST BE FULL
Y ENGA
GED
PRIOR T
O OPERA
TING THE
POWER SUPPL
Y
3
2
6
4
10
1
8
5
7
11
9