Catalyst 6500 Series Switches Installation Guide
OL-5781-04
Chapter 4      Removal and Replacement Procedures
  Removing and Installing the DC-Input Power Supplies
Step 3
Remove the two screws securing the outer terminal block cover, and remove the cover from the power 
supply. (See 
.)
Step 4
Remove the two screws securing the left inner terminal block cover, remove the cover, and set it aside. 
Remove one screw securing the right inner terminal block cover, remove the cover, and set it aside.
Note
You must remove three terminal block covers for the 4000 W DC-input power supply. The 
left-side inner terminal block cover has two securing screws, and the right-side inner terminal 
block cover has one securing screw.
Step 5
Remove the plastic insulator from over the terminal area.
 
.)
Step 6
Disconnect the DC-input wires from the terminal block in this order:
1.
Positive (+) 
2.
Negative (-) 
3.
Ground 
You must remove all DC-input wiring from both terminal blocks.
Note
You must remove DC-input wires from two terminal blocks for the 4000 W DC-input power 
supply (if both terminal blocks are used).
Figure 4-25 DC-Input Wire Connections for 4000-W DC-Input Power Supply
97535
3
INPUT OK
FAN
OK
OUTPUT
FAIL
I
0
1
2
Captive 
installation
screw
(   ) Ground
(+)  Positive
( - ) Negative
Power
switch
(   ) Ground
(+)  Positive
( - ) Negative
Plastic insulator
Power leads
attached to
terminal block
(+)   Positive
( - )  Negative
Power leads
attached to
terminal block
Plastic
insulator