Cisco CATALYST 6509E 9 SLOT 15U CHASSIS NO POWER SUPPLY NO FAN TRAY Specification Guide

Page of 336
4-38
Catalyst 6500 Series Switches Installation Guide
OL-5781-04
Chapter 4      Removal and Replacement Procedures
  Removing and Installing the DC-Input Power Supplies
Caution
Use both hands to install and remove the power supplies. Each DC-input power supply weighs 32 pounds 
(14.5 kg). 
Step 4
Grasp the power supply handle with one hand, and place your other hand underneath the power supply. 
Slide the power supply into the power supply bay. Make sure that the power supply is fully seated in the 
bay. (See 
Figure 4-29 Handling a 4000 W DC-Input Power Supply 
Step 5
Tighten the power supply captive installation screws. (See 
Step 6
Remove the two screws that secure the outer terminal block cover, and remove the cover from the power 
supply. (See 
.)
Step 7
Remove the two screws that secure the left inner terminal block cover, remove the cover, and set it aside. 
Remove one screw that secures the right inner terminal block cover, remove the cover, and set it aside.
Note
You must remove three terminal block covers for the 4000 W DC-input power supply. The 
left-side inner terminal block cover has two securing screws, and the right-side inner terminal 
block cover has one securing screw.
Note
You must install the plastic insulators that are shipped with the power supply.
Step 8
Place both plastic insulators over the terminal areas, aligning the circular holes in insulating cover with 
terminal posts. The protective end flap on the plastic cover is opposite the wire entry area. The protective 
end flap must fold down and cover the open side of the terminal (opposite side from wire entry). 
Note
Be sure to place a plastic insulator over the smaller terminal block, even if you are not attaching 
DC-input wires to it; this action ensures that the plastic insulator is available for future use.
104978
INPUT OK
FAN
OK
OUTPUT
FAIL
I
0
1
3
2
+
VE-1
-VE-1
+
VE-2
-VE-2
+
VE-3
-VE-3