RadioFrame Networks Inc DH2 User Manual

Page of 164
Method of Procedure 
Operations and Maintenance 
118 
RFN_3.1 Beta
 
Thermography (optional) 
A thermal scan should be done on all AC components associated with the DC 
power system. 
Perform thermal scans on all battery and DC power connections, DC buss-work, 
and circuit breakers. 
7.2.3 
Batteries 
Conduct the following annual maintenance
• 
Inspect Batteries: All cable connections and inter-cell connections. Check for 
oxidation at terminal posts and clean as required. 
• 
Check for leaks or seepage at terminal posts and battery jar seals. 
• 
Replace the battery jar if any leak or seepage. 
• 
Torque battery terminal and strap connections nuts and bolts to 
manufacturer’s specifications. Power Battery CSL-12100 Specification is 115 
in/lbs. 
• 
Verify battery voltage and mid-point voltage. 
• 
Perform Midtronics battery analysis using digital battery analyzer (optional). 
7.2.4 RadioFrame 
System 
Conduct the following semi-annual maintenance
• 
Visually inspect all RFS components for loose or foreign items and for visible 
damage. 
• 
Confirm that each component is receiving power (refer to the troubleshooting 
tables listed in 7.3 Corrective Maintenance, next in this chapter). 
• 
Verify that all RFS components are operational (refer to section 5.3.1.2 
Checking the Status of RFS Components). 
• 
Verify coverage validation by conducting spot tests described in section 5.4 
Coverage Validation. 
• 
Verify iDEN functionality by conducting spot tests using the procedures 
described in section 5.6 RFS Functionality Test. 
7.3 Corrective 
Maintenance 
The fault indications identified in this section provide a guide for isolating failures 
to a Field Replaceable Unit (FRU). The service technician should perform 
troubleshooting whenever a failure occurs during normal operation that cannot be 
resolved by the Operations and Maintenance Center (OMC).