Senstar Corporation LM100 User Manual

Page of 74
Senstar LM100 calibration
Senstar LM100 Product Guide
Page 55
1. Establish a connection between the UCM and the gateway.
2. On the Config tab, select the Profile button.
3. Verify that the All radio button is selected, and then select the Record button to begin 
recording the Sensitivity Profile.
4. At the luminaire AP, begin dragging the screwdriver along the fence fabric. Lift the screwdriver 
over the post at each fence post (i.e., do not strike the fence posts with the screwdriver). 
5. Maintain consistent pressure and a steady pace and continue dragging the screwdriver along 
the fence fabric at the same level height until reaching the end of the protected fence. 
6. Repeat this process, dragging the screwdriver from the end point back to the start point.
7. Select the Stop button to stop recording the Sensitivity Profile. 
8. Review the Sensitivity Profile to verify that it was successful.
9. Once you are satisfied with the profile, select the Update button to load the Sensitivity Profile 
data. If the recorded Sensitivity Profile is not acceptable, select the Undo button and repeat 
the profile procedure.
10. Close the Profile window and download the Sensitivity Profile data to the gateway.
Detection parameter setup
The Senstar LM100 detection parameters are setup globally through the gateway, and are applied 
to all of the luminaires. Senstar LM100 detection parameters include the Event Window, the Event 
Count and the Alarm Window. The Threshold is set independently for each defined luminaire 
segment.
Each LM100 installation includes many site-specific factors. Therefore, the system should be 
calibrated to meet the site’s detection requirements:
Adjust the Threshold to increase or decrease the detection sensitivity of the selected segment.
Specify the number of Events required to trigger an alarm.
Specify the period of time that must lapse before a subsequent Event will be recorded at the 
same location.
Specify the period of time in which a subsequent Event must occur. 
Note
If a sensitivity profile indicates a drop of 50 units within a 10 m length of 
the fence, it indicates that there is likely a problem at that location either 
with a luminaire or with the fence condition at that location (e.g., loose, 
sagging, stretched).
Tip
Senstar recommends that you save a UCM file that includes the 
recorded sensitivity profile. This can be useful for future maintenance 
and troubleshooting activities.
Note
The LM100 UCM Config tab includes an indicate button to assist in 
identifying specific luminaires. Select a luminaire, or a defined segment, 
select the indicate button, and the selected luminaire, or all of the 
luminaires in a segment, will flash 5 times.