4.1 Program Zones and Partitions
Now that you have enrolled the wireless devices, you should complete all zone
programming on the system. Although the exact programming required varies de-
pending on which control panel the RF5501-433 is connected to, you should check that
the following programming areas are completed correctly for each wireless zone:
• Enable zones and/or assign zones to one or more partitions (programming sections
[201]-[209], [201]-[265] for PC5020).
• Program the definition for each zone (programming sections [001]-[004]).
NOTE: WLS906 Wireless Smoke Detectors must be assigned to zones defined as Delay
24-hr fire (wireless) [87] or Standard 24-hr fire (wireless) [88] for proper supervision.
• Enable the wireless zone attribute for each wireless zone (PC580/585, PC1555/1565,
PC5008, PC5010 v2.0 and higher, PC5020, PC5015 v2.2 and higher only) (programming
sections [101]-[132]).
See your system 
Installation Manual, for more information on each of the above
programming sections.
4.2 Enable PC5132 Supervision
The control panel will supervise the PC5132 receiver portion of the RF5501-433 via the
Keybus after at least one device has been enrolled on the module (see section 3.2
“Enrolling Wireless Devices”).
To activate module supervision, after you enroll the first device(s):
1. Exit and then re-enter Installer Programming
2. Enter programming section [902]. Wait approximately 1 minute.
3. To exit press [#].
The system will generate a General System Supervisory trouble if the module is removed
from the Keybus. If you need to remove the PC5132 portion of the RF5501-433 module
from an existing system, you will have to disable supervision of the PC5132.
NOTE:  Deleting all devices from the RF5501-433 or defaulting the RF5501-433 will
cause a PC5132 supervisory fault.
To disable PC5132 supervision:
1. Disconnect the RF5501-433 from the Keybus
2. Enter [
✱][8][Installer Code]
3. Enter [902]. The control panel will clear all supervision and re-scan the system for
connected modules. The scan will take approximately one minute.
4. To exit press [#]
To review which modules the control panel is currently
supervising:
1. Enter [
✱][8][Installer Code]
2. Enter [903] to display all modules. On LED keypads, light [17] will indicate that the
PC5132 is present on the system. On LCD keypads, scroll until the module name
appears on the display
3. To exit press [#]
S E C T I O N  4
Other Programming