Digital Security Controls Ltd. 05SKYCL User Manual

Page of 28
10
Programming Descriptions
[02]
Mode 2 - (2) 24-Hour Zones
In this mode, the YEL and GRN
terminals on the Skyroute
CL3050 will be used as zone
inputs.  These zones will support
the DSC standard EOL configura-
tion and loop response.  Pro-
gramming sections will allow the
installer to change the default
zone types and attributes. The
Skyroute CL3050 will continu-
ously monitor these zones and
transmit any alarms that occur to
the central station.
NOTE: Use Mode 2 for UL residential burglary installations.
[03]
Mode 3 - (8) 24-Hour Zones
In this mode, the Skyroute
CL3050 is connected to a
PC5108 zone expander using the
corresponding RED, BLK, YEL and
GRN terminals.  The Skyroute
CL3050 will drive the Keybus to
communicate with the PC5108.
A +12V
DC
 supply connected to
the RED and BLK terminals is
required when using this mode.
The Programming sections allow the installer to change the default zone types
and attributes. The Skyroute CL3050 continuously monitors these zones and
transmits any alarms that occur to the central station.
NOTES:  This configuration can not be used with an AC supply.
Jumpers on the PC5108 must be set as follows:
J1
J2
J3
ON
OFF
ON
J4
J5
J6
OFF
OFF
ON
Default - [01 -03]  dependant on start up configuration.
NOTES:  Use Mode 3 for UL Installations.
PC5108 must be installed in its own enclosure or in the same cabinet as the con-
trol panel.
All connections are power limited.
[11] Skyroute CL3050 Configuration Options 1
Option 1 - A Channel Selected/ B Channel Selected. 
All Modes
This Option determines whether cellular channel “B” or channel “A” is used. In
Canada, Channel B is used (Default). In the USA refer to the SID list for the chan-
nel of the cellular service provider in your area. Default - Channel B
Option 2 - Normally Closed Loops/ End-of-line Resistors                Mode 2, 3
Normally Closed Loops can be wired as shown. Multiple Normally Closed con-
tacts can be wired in series. For Double or Single EOL resistors this option must be
set to OFFDefault - Normally Closed (N/C) Loops.
NOTE: Option must be OFF for UL Installations.
Input Voltage
10.6-14 V
or V
AC
DC
Zone 1 Input
Zone 2 Input
Zone Common
Trouble Output
RED    BLK
YEL    GRN   COM   PGM
RED    BLK
YEL    GRN   COM   PGM
+12 V
DC
Ground
To Keybus
Connections
on PC5108
System Common
Trouble Output