Digital Security Controls Ltd. 05SKYCL User Manual

Page of 28
4
Quick Start
5
Mount Unit
Remove the front cover if required
Disconnect flying leads from battery and power leads from the RED and BLK 
terminals (if connected).
Remove two screws securing battery clamp. Remove battery
Mount backplate of unit to wall or over electrical junction box using the 
four screws provided.
NOTE: DO NOT connect the battery to the flying leads and AC or DC power to
the terminal strip until all other wiring connections are completed.
Route wiring through the access holes provided and connect to terminal 
strip.
Power up unit by connecting battery and power source.
Front cover is to be securely fastened with screw provided.
6
Enroll Unit
Call Connect 24 and Enroll the Skyroute CL3050. Refer to back of Front Cover 
for contact information and a list of information required to complete the enroll-
ment with the Connect 24 Voice Response Unit.
2.2 Testing
Program Mode: If you have wired the unit to power up in the programming 
mode. Follow the steps outlined in Section 6, Programming Descriptions and 
record the program settings in Section 7, Programming Worksheets.
Test Transmission - Pressing and holding the enroll button for 2 seconds will 
send a test transmission to the central station via Connect 24. Refer to Enroll 
Button
 
in Section 3, Controls and indicators for test transmission details.
Mode 1: Disable the telephone line connected to the control panel. Simulate 
Burglar and Fire Zone violation. Verify that the Skyroute CL3050 transmits the 
events to the central station.
Mode 2 & 3: Simulate Faults, Tampers, and Zone violations in accordance with 
the settings outlined in Sections 6, Programming Descriptions. Verify that the 
Skyroute CL3050 transmits the events to the central station.
2.3 Resetting to Factory Defaults
NOTE: Resetting to factory defaults is required to change mode of operation. 
Remove Power from the Skyroute CL3050; disconnect battery and control 
panel if applicable (mode 1).
Disconnect all wiring from the YEL and GRN terminals.
Connect a jumper wire between the YEL and GRN terminals.
Apply power to the system.
NOTE: When the hardware default has been completed; the yellow, green and
red LEDs will flash on and off continuously. 
Remove power from the system.
NOTE:  To resume communications with Connect 24,  Section [11], Option 6
must be set to ON. To do this; the system must be powered up in programming
mode. Refer to Section 5 System Programming.
Reconnect all original wiring and reapply power to the system.
Test System - Refer to Section 2.2