Enter the Ethernet Gateway IP address of the dual communicator. The address must be entered as a dotted decimal number (e.g. 
192.168.1.100).  Each three-digit segment of the address must be within a valid range of 000 to 255.  The gateway is used in the 
event that the destination address is not on the local network. The data will need to be sent through a router device. This is the 
address of that router device.
Option 004: Receiver Supervision Interval
Default (0000)
When receiver supervision is enabled (Option 005, bit 1 and bit 2) the unit sends heartbeats to Ethernet Receiver 1 and GPRS 
Receiver 1 to indicate that it is still running. Use Option 004 to set the interval time at which heartbeats are sent. Receiver Supervi-
sion Interval window times are listed in the table below. 
The value you enter for Option 004 must be within the window time stated.
Option 005: System Toggle Options
Default ()
Table 6: Window Times
Jurisdiction
Window
UL CF
5min w/90sec heartbeats
UL CB
200sec
UL RF
30 days
UL RB
200 sec
ULC CB
180sec w/90sec heartbeats
ULC CF
180sec
Table 7: System Toggle Options
Valid Data Range
Effect
Default
Bit 1
Ethernet Receiver 1 Supervised*
Disabled (Off)
Bit 2
GPRS Receiver 1 Supervised*
Disabled (Off)
Bit 3
Supervision Type:
On - Commercial Supervision
Off - Residential Supervision
Disabled (Off)
Bit 4
Primary Comms Channel - by default the primary path is Ethernet, then 
GPRS; this can be reversed by enabling bit 4
On - GSM
Off - Ethernet
Disabled (Off) 
Ethernet 
Enabled (On) 
GSM 
Bit 5
Redundant Communications - sends events at the same time over receivers 
1 and 3, 2 and 4 (Ethernet/GPRS)
Disabled (Off)
Bit 6
Remote Firmware Upgrade - via Ethernet 
Enabled (On)
Bit 7
UL Remote Firmware Upgrade - triggered by an onsite event
Disabled (Off)