Digital Security Controls Ltd. 18LE2077 User Manual

Page of 51
13
NOTE: Add a single ‘F’ as a suffix to the 4 digit hex number to populate the unused remainder of 
the 32 character field.
5. Panel Section [350]: If any of the phone numbers have been programmed as DCAA, DCBB,
DCCC, DCDD, or DCEE, panel Section [350] must be set to [04] if SIA format or [03] if
Contact ID (CID) format is used by control panel.
6. Panel Section [382]: Toggle Option [5], ‘GS/IP Module Enabled’, must be set to ON.
7. Panel Section [401]: Toggle Option [1] must be set to ON in order to perform panel DLS
session through Cellular or Ethernet data channel.
8. Panel section [310], account code, auto syncs with the communicator account code in
section  [021]. The panel account code ([*][8][installer code] [310]), will overwrite the
communicator account code section ([*][8][installer code] [850]  [021]) if programmed
differently.
NOTE: Keep a record of the SIM card telephone number, it is required by users for SMS 
Command and Control functions. (The number can be recorded in the Programming 
Worksheets Section of this document, under Option [996]). Due to the nature of the SIM card 
activation process with Cellular network carriers, it can take up to 24 hours for SIM card 
activation to be complete.
SMS C
OMMAND
 
AND
 C
ONTROL
 F
UNCTIONS
SMS Command and Control is available on SCW9055/57 panels. Users can send SMS text 
messages from their mobile phone to the GSM phone number assigned to their system. Com-
mands are only accepted from telephone numbers that have been programmed in Sections 
[311]-[318]. The system will reject messages sent from telephone numbers that are not on the 
programmed list.
When the received SMS text matches a valid Section message, the function is performed on 
the control panel. Text messages are not case sensitive and extra spaces are ignored. A User 
Access Code may be required for some SMS messages.
The SMS Message format is in 3 parts: Command, Partition Label (or only the partition number), 
and Access Code.
If an Access Code is included in the message, it is sent to the control panel for validation, along 
with the requested function.
If the panel is configured to require an Access Code and the code is not sent (or invalid) the 
panel will fail the function (unsuccessful).
If the panel fails the function, an SMS response message is sent to the user. The SMS response 
will echo the command sensat, followed by the label “unsuccessful”. (e.g., “night arm partition 2 
1234 unsuccessful”).
The partition label or partition number may be excluded from the SMS request in a single parti-
tion system (e.g., disarm 9123).
NOTE: The GSM phone number can be viewed in Section [851] [996], and/or [851] [229] or 
by entering *6, then scrolling down to “SMS Programming” and scrolling down to “Cellular 
phone No”.
L
ABEL
 P
ROGRAMMING
 for SMS M
ESSAGE
Programmable Labels can not be modified in Connect24, use DLS IV for label programming 
only, if labels need to be modified. Before initiating remote programming, record your network’s 
Public IP Address and port for incoming DLS IV connections.
1. Run the DLS IV software on your computer. DLS IV will connect to the unit, using the Public IP
address, and make an Ethernet connection. If the Ethernet connection fails, DLS IV will report
an error and prompt you to connect using Cellular.