Household Fire Warning System ANSI/UL 985  NFPA 72 Specifications
22.1  Bell Output Definition
The bell output of the Model XT30/XT50 must be programmed to operate steady on burglary alarms and
pulsed on fire alarms. See the XT30/XT50 Programming Guide.
22.2  Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
22.3  Household Fire Warning
Recognized limited energy cable must be used for connection of all initiating, indicating, and supplementary
devices.
22.4  Wireless External Contact
When used, the External Contact of 1101 or 1102 must be programmed Normally Closed. See the XT30/
XT50 Programming Guide.
22.5  Wireless Supervision Time
The Zone Information Supervision Time must be 3 minutes for fire devices. See the XT30/XT50 Programming
Guide.
22.6  Wireless Fire Verification
When used, the Model 1161 and 1162 wireless smoke detectors must not be programmed as Fire Verification
(FV) zone type. See the XT30/XT50 Programming Guide.
California State Fire Marshal Specifications
23.1  Bell Output Definition
The bell output of the Model XT30/XT50 must be programmed to operate steady on burglary alarms and
temporal on fire alarms.