XTL Installation Guide
10
ComPlIanCe
Central Station Burglar Alarm Units 
ANSI/UL 1610
16.1  Standard Line Security
Standard Line Security is provided when the Check-in time is set to 3 minutes. When programmed for
Standard Line Security, Exit Time Restart is disabled.
Note: The SecureCom Wireless text plan selected for the panel should match or exceed the programmed
Monthly Limit or additional cellular charges may apply.
16.2  Remote Disarm
REMOTE DISARM must be programmed as NO.
16.3  Central Station
MESSAGE TO TRANSMIT programming for zones must not be set to LOCAL (L).
Household Fire Warning System  
ANSI/UL 985  NFPA 72 Specifications
17.1  Bell Output Definition
The bell output of the XTL panel must be programmed to operate steady on burglary alarms and temporal
on fire alarms. See the XTL Programming Guide.
17.2  Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
17.3  Wireless External Contact
When used, the External Contact of 1101 or 1102 must be programmed Normally Closed. See the XTL
Programming Guide.
17.4  Wireless Supervision Time
The Zone Information Supervision Time must be 3 minutes for fire devices. See the XTL Programming Guide.
17.5  Wireless Fire Verification
When used, the Model 1161 and 1162 wireless smoke detectors must not be programmed as Fire Verification
(FV) zone type. See the XTL Programming Guide.
17.6  Battery Standby
For UL listed applications, the panel must have 24 hour battery standby operation.
17.7  Test Frequency
The Test Frequency option must be programmed to send a report at least once every 30 days.