XTL Installation Guide 
Digital Monitoring Products
11
ComPlIanCe
False Alarm Reduction Programmable Options ANSI/SIA CP-01-2007
18.1  Shipping Defaults and Recommended Programming
SIA CP-01 FEATURE 
PARAGRAPH # AND 
DESCRIPTION
DMP PROGRAMMING 
GUIDE LT-1108 
SECTION #
REQUIREMENT
RANGE
SHIPPING 
DEFAULT
RECOMMENDED 
PROGRAMMING*
4.2.2.1 Exit Time
8.6 Exit Delay
Required 
(Programmable) 45 sec. - 250 sec.
60 
Seconds
60 Seconds
4.2.2.2 Progress
Annunciation 
13.14 Prewarn
Address
Allowed
Individual keypads
may be disabled per 
zone
All 
keypads
enabled
All keypads enabled
4.2.2.3 Exit Time
Restart
8.6 Exit Delay
Required Option For re-entry during 
exit time
Enabled
Enabled
4.2.2.5 Auto Stay Arm
on Unvacated Premises
8.17 Occupied
Premise - 
See Install
Guide
 
Required Option
(except for
remote arming)
Occupied Premise
NO/YES option
Enabled
Enabled Yes
for Residential 
Applications
4.2.4.4 Exit Time and
Progress Annunciation/
Disable - for Remote
Arm
Not Available on
Remote Arming
Allowed Option
Progress Annunciation 
Always disabled for 
Remote Arming
Not
Available
Remote Arming not 
allowed for CP-01 
installations.
4.2.3.1 Entry Delay(s)
8.5 Entry Delay
Required 
(Programmable) 30 sec. – 240 Sec. **
30
Seconds
At least 30 Seconds
**
4.2.5.1 Abort Window –
for Non-Fire Zones
3.3 Transmit Delay
Required Option Disable by zone or
zone type
Enabled
NT DY
EX Zone
Enabled
4.2.5.1 Abort Window
Time – for Non-Fire
Zones
3.3 Transmit Delay
Required 
(Programmable)
20 sec., 30 sec., or
40 sec.
** 
30
Seconds
At least 20 Seconds
**
4.2.5.1.2 Abort
Annunciation
3.3 Transmit Delay
Required Option
Annunciate that 
no alarm was 
transmitted 
Yes
Yes
4.2.5.4.1 Cancel
Annunciation
Always Enabled - Not
Programmable
Required Option
Annunciate that 
a Cancel was 
transmitted (S49)
Always 
Enabled
Yes
4.2.6.1 & 4.2.6.2
Duress Feature
User Code + 1 =
Ambush Code Not
Available
Allowed Option
No 1 + derivative of
another user code/no 
duplicates with other 
user codes
Code +1
Always 
Disabled
Not Programmable
4.3.2 Swinger Shutdown Not Available —
Always On
Required 
For all non-fire
zones, shut down
after 1 trip
Always 
On
Always On
4.3.2 Swinger Shutdown
Disable
13.13 Swinger Bypass Allowed 
For non-police 
response zones
Yes
Enabled (all zones)
4.3.3 Fire Alarm
Verification
13.5 Zone Type
Required Option FV Type Zone
No
Yes as required 
(unless sensors can
self verify)
* Programming at installation may be subordinate to other listed requirements for the intended application. 
** For listed Installations, combined Entry Delay and Transmit Delay should not exceed 1 minute.