Digital Monitoring Products Inc PC0117 User Manual

Page of 18
Digital Monitoring Products
 
XTL Installation Guide
12
ComPlIanCe
False Alarm Reduction Programmable Options ANSI/SIA CP-01-2007 
(continued)
18.2  Entry Delay
Only use Entry Delay 1. Do not use Entry Delay 2. See the XTL Programming Guide.
18.3  Local Bell
All non-fire zones such as Night, Day, Exit, Aux1 and Aux 2 must be programmed for local bell enabled with
a bell cutoff time set to a minimum of 6 minutes to provide a cancel window of 5 minutes or greater.  This 
does not apply to manually operated zone types such as Panic and Emergency.
The requirements are superceded by any requirements for Commercial Burglar, Household Fire Warning, or
Household Burglar applications.
18.4  Minimum Installation Requirements
SIA CP-01-2007 minimum system installation requirements include an XTL, an 1135 Wireless Siren, and
communication to an SCS-1R receiver plus a 9000 Series Wireless keypad.