Digital Monitoring Products Inc PC0128 User Manual

Page of 31
Digital Monitoring Products
 
XT30/XT50 Installation Guide
22
TroubleshooTing
Wiring Diagrams
28.1  Multiple Indicating Circuit Modules Installation
J3
Phone 
Li
ne
O
utputs
J11
1  2  3  4
J1
Ethernet
J16 Reset
J20
Wi
rel
ess 
Antenna  connecti
on
J7 
RJ
 
Supervision
J24 
Cel
lul
ar 
header 
J18 Load
RED
Pr
ogr
ammi
ng
J8
S
AUXILIARY
  POWER
  SUPPLY
12 or 24 VDC
5
Amp Maximum
  Power Suppl
y
Tr
ouble Contacts
          N/C
NOTE: If an auxiliary supply is not used,
terminals 3 and 4 on the 866 Indicatin
g
Circuit Module can be jumpered together
to supply bell power from the XT30 panel.
Each 866 Indicating Circuit Module
in alarm draws up to 35mA from its
terminal 3 alarm input.
The
Auxiliary Power Supply and Indicating Circuit Module
trouble contact zone must be programmed as a Supervisor
y
T
ype zone and must be selected for display in the keypad
status list.
= Supervised Circui
t
S
1
2
3
4
5
6
7
8
Auxiliary Power
Ground
Alarm Input
Bell Power + Input
Bell Power Ð Input
B
ell
+ Output 
-
B
ell
Ð Output
Bell B + Output
Bell T
rouble
Bell T
rouble
Bell B Ð Output
9
10
11
UL
 Listed, Polarized
Indicating Devices.
S
tyle 
Z
Notification Circuit Modul
e
DMP Model 865
85mA at 12 VDC
AUXILIARY
  POWER
  SUPPLY
  Power Suppl
y
T
rouble Contacts
          N/C
12 or 24 VDC
5 Amp Maximum
S
S
1
2
3
4
5
6
7
8
Auxiliary Powe
r
Ground
Alarm Input
Bell Power Input
B
ell Output 
+
B
ell Output 
-
Bell T
rouble
Bell T
rouble
UL
 Listed, Polarized
notification Devices.
10k
W
 EOL
 Resistor
  DMP
 Model 308
Notification Circuit Modul
e
 DMP Model 866
  37mA at 12 VDC
1k
W
Optional Module installation
Each 865 Notification Circuit Module
in alarm draws up to 85mA from its
terminal 3 alarm input.
S
S
S
S
S
S
S
S
S
S
Style 
W
S
S
S
S
S