Digital Monitoring Products Inc PC0128 User Manual

Page of 31
XT30/XT50 Installation Guide 
Digital Monitoring Products
21
COMPLIANCE
Troubleshooting
27.1  Troubleshooting Section
This section provides troubleshooting information for use when installing or servicing an XT30/XT50 system.
Problem
Possible Cause
Possible Solutions
Keypad displays “SYSTEM TROUBLE”
J16 Jumper is installed.
Remove the J16 reset jumper.
Open or short on the green data wire to
the keypad.
Check for broken or shorted wires between
the panel and the keypad.
Bad keypad or zone expander is affecting
the Green data wire.
Replace keypad or zone expander.
Keypad keyboard is not functional. 
When a key is pressed, only a short
beep is emitted.
Open or short on the yellow data wire to
the keypad.
Check for broken or shorted wires between
the panel and the keypad.
Bad keypad or zone expander. is affecting
the Yellow data wire.
Replace keypad or zone expander.
Keypad XMIT Green LED is off
Panel is reset.
Remove J16 jumper.
Flash Load enabled.
Remove J18 jumper and reset panel.
Keypad RCV Yellow LED is off
Keypad/expanders are not connected to panel. Connect keypad/expanders.
Keypad/expanders are greater than five.
Check keypad/expanders address.
Keypad beeps when keys are pressed,
but will not allow the user to arm or
disarm, or enter the User Menu.
Two or more keypads are assigned to the
same address.
Set each keypad on the system to a unique
address.
Power LED is off.
AC/Battery is not connected.
Connect AC power and/or battery.
Overcurrent OVC LED turns Red
Too many devices attached to auxiliary.
Maximum current draw is 500 mA.
Wireless Green TX LED is off.
Wireless House Code is not programmed.
Program House Code in System Options.
Wireless Yellow RX LED never flashes.
Transmitters are not getting through to
receiver.
Check transmitter serial numbers.
Move transmitter closer.
If XT30, replace 1100 series receiver.
Wireless Green TX and Yellow RX
LEDs are both on steady
Panel is reset.
Remove J16 jumper.
Flash Load enabled
Remove J18 jumper and reset panel.
Keypad operates intermittently, 
keystrokes may be missed, or display 
does not update consistently.
Wire length may exceed maximum,
resulting in poor data performance.
Wire length can be reduced or a heavier
gauge used.
A power supply can be added near the keypad.
Aee LT-2031, LX-Bus/Keypad Bus Wiring
Application Note for more information.
27.2  Common LCD Keypad Displays
Listed below are several keypad messages you may see on the display. Follow the instructions in the Possible
Solutions column to correct the problem.
Message
Meaning
Possible Solutions
INVALID CODE
The user code entered is not recognized by the system. Check the user code and try again.
CLOSING TIME
The system was not armed at its scheduled closing
time. 
Users still on the premise should arm the system or
extend the schedule to a later time.
AC TROUBLE
The system is not getting proper AC power.
Check that the AC connections are good from the
transformer.
BATTERY TROUBLE
The battery is either low or missing.
Check to see that battery and connections are good.
SYSTEM BUSY
The system is performing another task with a
higher priority or is being Remote Programmed.
Wait a few moments for the system to complete the
task. Make sure the J16 jumper is not on the panel. If
the message displays for several minutes, the keypad
is not receiving polling from the panel.
TRANSMIT FAIL
The panel has attempted to communicate with
the central station multiple times and has not
succeeded.
Verify your communication type, account number,
and phone number. Make sure the telephone line is
connected and working properly.