Digital Monitoring Products Inc PC0134 User Manual
Digital Monitoring Products
1183 Detector Installation Guide
2
Selecting the Proper Location
(LED Survey Operation)
For optimum wireless performance, install the transmitter away from large metal objects. Mounting the transmitter
on or near metal surfaces impairs performance. The 1183 Series transmitters provide a survey capability to allow
one person to confirm transmitter communication with the receiver. The 1183 transmitter PCB Red Survey LED
turns on whenever data is sent to the receiver then immediately turns off when the receiver acknowledgement is
received. The survey button is located within the battery compartment and the transmitter survey LED can be seen
near the survey button location. When the transmitter does not receive an acknowledgement from the receiver
the LED remains on for about 8 seconds to let you know communication is not established. Communication is also
faulty when the LED blinks multiple times in quick succession. Relocate the transmitter or receiver until the LED
immediately turns off indicating the transmitter and receiver are
communicating properly.
Test the communication between the control panel and the detector
Test the communication between the control panel and the detector
before permanently mounting the detector as follows:
1. Program the transmitter into the panel. See Programming
Transmitter in the Panel. Install the battery.
Note: Survey operation requires that the detector have the mounting
base installed to engage the tamper switch.
2. Hold the detector up in the location where you plan to install it.
3. Press the survey button (See Figure 2) to send data to the receiver
3. Press the survey button (See Figure 2) to send data to the receiver
to confirm operation.
General Location Guidelines
In addition to NFPA 72, use the following location guidelines to optimize performance and reduce the chance of false
In addition to NFPA 72, use the following location guidelines to optimize performance and reduce the chance of false
alarms from the detector:
• Locate ceiling-mounted detectors in the center of a room or hallway at least 4 inches from any walls or partitions
• Locate wall-mounted heat detectors so the top of the detector is 4 to 12 inches below the ceiling
• Mount the detector on a firm permanent surface
• Locate the detector in environmentally controlled areas where the temperature does not exceed 100° F (7.8° C).
• In rooms with sloped, peaked, or gabled ceilings, locate detectors 3 feet (.9 meters) down or away from the
• Locate wall-mounted heat detectors so the top of the detector is 4 to 12 inches below the ceiling
• Mount the detector on a firm permanent surface
• Locate the detector in environmentally controlled areas where the temperature does not exceed 100° F (7.8° C).
• In rooms with sloped, peaked, or gabled ceilings, locate detectors 3 feet (.9 meters) down or away from the
highest point of the ceiling
• When mounting to suspended ceiling tile, the tile must be secured with the appropriate fastener to prevent
tile removal
Installing the Detector
Note: When setting up a wireless system, it is recommended
to program zones and connect the wireless receiver before
installing batteries in the transmitters.
Install the Mounting Base
Install the Mounting Base
1. Using the two screws provided, mount the base in the
location previously surveyed for proper communication.
Attaching and Removing the Detector
1. Using the alignment notch on the lip of the mounting
base as a guide, align the detector with the alignment
tabs.
2. Insert the detector into the mounting base and turn
clockwise approximately 15 degrees. It should snap
firmly into place.
To remove the detector from the mounting base, grasp the
detector and turn it counterclockwise approximately 15
degrees. The detector should snap off of the mounting base.
See Figure 3.
Alignment
Tabs
Alignment
Tabs
Mounting Holes
Alignment Notch
Figure 3: Mounting Base
Figure 2: Survey Button
Survey
Button
Survey
LED
SURVEY