Digital Monitoring Products Inc PC0134 User Manual

Page of 4
1183 Detector Installation Guide 
Digital Monitoring Products
3
Installing or Replacing the Batteries
Observe polarity when installing the battery.  Use only 3.0V lithium batteries,  DMP Model CR123-FIRE or Panasonic 
Model CR123A.    
Note: When setting up a wireless system, it is 
recommended to program zones and connect 
the receiver before installing batteries in the 
transmitters.
1.  Slide the battery compartment cover away 
from the detector to unsnap it and lift it off.  
See Figure 4.
2.  If replacing the battery, remove the old 
battery and dispose of them properly.
3.  Observing correct polarity, insert the new 3V 
lithium battery into the battery compartment 
and replace the cover.  Use only new 
batteries when replacing old ones.
4.  Reattach the detector to the mounting base.  
See Attaching and Removing the Detector.
5.  Test the detector.  See Testing the Detector.
  Caution: Properly dispose of used batteries. Do not recharge, disassemble, heat above 212°F (100°C), or 
 
incinerate.   Risk of fire, explosion, and burns.
Testing the Detector Alarm
The 1183 Series detectors provide a test button to verify the detector operation.  
1.  To test the detector, first enable Walk Test operation on the control 
panel.  If the system is monitored, the system sends a System Test Begin 
report (System message S66) to the central station.  
 
To conduct the Walk Test, reset the control panel by momentarily 
placing a jumper on J16.  From the keypad, enter the code 8144. The 
keypad displays WALK TEST.  Refer to the panel programming guide for 
complete information on Walk Test operation.
2.  For the XTL or XT30/XT50 Series panels, select STD (Standard Walk Test).  
For the XR100/XR500 Series panels, select FI (Fire zones).  A sensor reset 
occurs after each detector tested.
3.  Remove the cover over the test button opening and insert a small 
screwdriver in the test button opening and press the test button.  The 
detector sends an alarm signal to the control panel.  Verify that the walk 
test trip counter increments to indicate a successful test.  Once testing 
is completed, replace the cover over the test button opening.
4.  Select END to stop the Walk Test.  When the Walk Test ends or a 
20-minute time-out expires, a final Sensor Reset occurs. The System Test 
End message (System message S67) is sent to the central station along 
with verify and fail messages for each zone under test.  Faulted zones 
then display on the keypad.
Important: The control panel alarm and all auxiliary functions should be verified for a complete test of the system.  
See the panel programming guide for additional information.
Battery Life Expectancy
Typical battery life expectancy for DMP wireless heat detectors is at least 2 years.  DMP wireless equipment uses 
two-way communication to extend battery life.  
The following situations can reduce battery life expectancy:
•  If a receiver is unplugged or not installed.
•  Frequent transmissions, such as how often the detector is tested.
•  When installed in extreme hot or cold environments.
Figure 4: Battery Compartment
Battery
Compartment
Battery Cover
Battery
Detector Cap
Mounting Base
Test Button
Alignment
Notch
Tamper Post
Detector Cover
Battery Compartment
Heat
Collector
Fin
Figure 5: Test Button