Digital Monitoring Products Inc PC0181 User Manual

Page of 58
Digital Monitoring Products
 
XTLplus Installation and Programming Guide
40
APPENDIX
Appendix
This section provides additional zone and system information.
36.1  Status List
The Status List is the current status of the system or records of recent system events that display on 
alphanumeric keypads. For example, in Home/Away systems you may see the display 
SYSTEM READY.
If an event were to occur on the system, such as an AC failure, the keypad would also display the 
AC  POWER   
-TRBL message. This is a system event that is placed into the Status List to alert the user to a problem with 
the system.
Some Status List items remain in the display until manually cleared and some are cleared automatically 
when the condition returns to normal. Below is a list of status and event displays the keypad can show in the 
Status List:
Description 
Must be manually cleared?
Fire and Supervisory zone alarms 
Yes - by Sensor Reset
Fire and Supervisory zone troubles 
No - clears when zone restores
Burglary zone alarms 
No - clears at disarming.
All other zone alarms 
No - clears when zone restores
Zone monitor displays 
No - clears after approximately 8 minutes
Day zone alerts 
No - clears after approximately 8 minutes
System monitor troubles 
No - clears when condition restores 
(AC and battery trouble)
Armed status display 
No 
(System On)
Disarmed status displays 
No 
(System Ready, System Not Ready)
Remote keypad messages 
No 
(Sent to the keypad by your office or central station)
The highest priority message is displayed on the keypad. When there are multiple items in the list, you can 
use the COMMAND or Back Arrow keys to scroll forward or back through the items.
36.2  Transmission Delay
You can set Abort Reports to 
YES if Opening and Closing reports are not being sent.
If the area where the alarm occurred is disarmed during the Transmit Delay time, only an Abort Report (S45) 
message is sent to the receiver. If the area where the alarm occurred is disarmed after the alarm message 
is sent to the receiver but before the Bell Cutoff time expires, even if the alarm was silenced, an Alarm 
Cancelled (S49) message is sent. The Alarm Cancelled report cannot be disabled.
36.3  False Alarm Reduction
System Recently Armed report
The System Recently Armed report (S78) is sent when a burglary zone goes into alarm within two minutes of 
the system being armed.
36.4  Diagnostics Function
The XTLplus panel contains a Diagnostics function that allows you to test the integrity of the network 
communication, integrity of the cellular communication and cellular signal communication of the 265C to 
the nearest tower for the cellular carrier. The Diagnostics function also displays the panel settings. To use 
Diagnostics, reset the panel, enter the Diagnostics code 2313 (DIAG), and press COMMAND.
MAC Address
Short for Media Access Control address. This hardware address uniquely identifies each network node. Not 
to be confused with an IP address, which is assignable. In the Diagnostics function, the MAC address is the 
panel on-board network hardware address. Press any select key to display the panel MAC address. Press the 
COMMAND key to view the next option.
Serial Number
This number is the network communicator serial number. Reference this number for communicator date-of-
manufacture, hardware version, etc. Press any select key to display the Serial Number. Press the COMMAND 
key to view the next option.