XTLplus Installation and Programming Guide
38
ZONE INFORMATION
the panel sends only a fault report from the first zone to the receiver.
Note: If CRS ZONE is YES, a valid CRS ZN TIME must be programmed in System 
Options for this feature to be enabled.
Cross-zoning is not compatible and cannot be enabled for Fire Verify  
zone types.
33.16 Priority
Selecting 
YES allows you to provide additional protection for a zone by requiring it 
to be in a normal condition before its assigned area can be armed. A priority zone 
cannot be bypassed.
A Priority zone not in a normal condition cannot be armed. If a user attempts to 
arm the area, the keypad displays the bad zone name followed by 
PRIORITY ZONE 
and the arming is stopped.
33.17 
Traffic Count
This option is displayed for NT or EX type zones. Select 
YES to provide reporting 
to the receiver of the number of zone trips while in a disarmed state. The number 
of trips for each zone set as traffic count are added together and included with 
the area closing message and reported to the central station automation system. 
Default is NO.
33.18 
Zone Audit Days
Enter the number of days (0 to 99) allowed to elapse without the zone being 
tripped before a fault message is sent. The message is sent to the receiver(s) 
programmed to receive Supervisory/Trouble Reports at 10:00 am following the 
expiration of the timer. Each time the zone is tripped, the Zone Audit Days timer 
restarts and begins to countdown the number of days programmed. After the 
countdown expires, a fault message is sent and the Zone Audit Days timer restarts 
and begins to countdown the number of days programmed. Available for all zone 
types except fire and fire verify. Enter 0 (zero) to disable this function. Default is 0 
(zero).
33.19 
Receiver Routing
This option displays if Zone Type is set for Auxiliary 1 or Auxiliary 2.
Press any top row key to select the Receiver Routing for the selected zone.
• Select NORM to send Alarm and Supv/Trbl messages from this zone to receiver 1 
or receiver 2 as programmed within the receiver.
• Select 1 to send Alarm and Supv/Trbl messages from this zone to receiver 1 only, 
regardless of the programming for that receiver.
• Select 2 to send Alarm and Supv/Trbl messages from this zone to receiver 2 only, 
regardless of the programming for that receiver.
• Select BOTH to send Alarm and Supv/Trbl messages from this zone to both 
receivers, regardless of the programming for either receiver.
33.20 
Zone Number
Enter the zone number you want to program next. Return to section 32.1 and 
follow the descriptions of each programming option. If all zones are programmed, 
press the ARROW key at the 
ZONE NO: – display to continue.
Stop
34.1 Stop
PRIORITY  NO YES
TRAFFIC COUNT
    
 
NO YES
ZONE AUDIT DAYS:
    
0 - 0
RECEIVER ROUTING
NORMAL
NORM 1 2 BOTH
ZONE NO: -
 
                00
STOP