Digital Monitoring Products Inc PC0181 User Manual

Page of 58
Digital Monitoring Products
 
XTLplus Installation and Programming Guide
44
APPENDIX
36.8  Zone Type Descriptions
This section describes applications for the default zone types in Zone Information programming.
NT (Night Zone) - Controlled instant zone used for perimeter doors and windows and interior devices such as 
PIRs and glassbreak detectors.
DY (Day zone) - Used for emergency doors or fire doors to sound the keypad buzzer and display the zone 
name when the zone is faulted. Day zones also will send alarm reports to the receiver during the system’s 
armed periods.
EX (Exit zone) - Initiates the entry delay timer when its assigned area is fully armed. Also, can initiate an 
exit delay timer to allow a user to exit an area after the arming process has started.
PN (Panic zone) - Used for connecting to mechanical devices that allow a user to signal an emergency alarm. 
Panic zones can provide either a silent or audible alarm with or without reporting to a central  
station receiver.
EM (Emergency zone) - These are used for reporting medical or other non-panic emergencies to the  
central station.
SV (Supervisory zone) - Used to provide 24-hour zone supervision. Typical applications are high water, and 
low and high temperature gauges.
FI (Fire zone) - Used for any type of powered or mechanical fire detection device. Typical applications are 
for smoke detectors, sprinkler flow switches, manual pull stations, and beam detectors.
FV (Fire Verify zone) - Used primarily for smoke detector circuits to verify the existence of an actual fire 
condition. When a Fire Verify zone initiates an alarm, the panel performs a Fire Reset. If any Fire zone 
initiates an alarm within 120 seconds after the reset, an alarm is indicated. If an alarm is initiated after 120 
seconds, the cycle is repeated.
A1 and A2 (Auxiliary 1 and Auxiliary 2) - These zones are similar to a Night zone and are typically used to 
protect restricted areas within a protected premises. Auxiliary 2 zones do not appear in the Status List.
AR (Arming zone) - Allows you to connect a keyswitch to a zone and use it to arm and disarm the system.