Digital Monitoring Products
 
XTLplus Installation and Programming Guide
46
APPENDIX
36.10 Common Keypad Messages
Message
Meaning
Possible Solutions
INVALID CODE
The user code you have entered is not 
recognized by the system.
Check the user code and try again.
CLOSING TIME 
The schedule has expired but the 
system has not been armed.
Users still on the premise should arm the system 
or extend the schedule to a later time.
KEYPAD NAME - NOPWR Wireless keypad is not getting proper 
power.
Check that AC/DC transformer is plugged in 
correctly.
AC TROUBLE
The system AC is low or missing.
Check that the AC connections are good.
BATTERY TROUBLE
The System battery is either low or 
missing.
Check that the battery connections are good 
and the battery is still good.
SYSTEM TROUBLE or 
SERVICE REQUIRED
There is a problem with one or more 
components in the system.
Press the RESET button for 1-2 seconds.
SYSTEM BUSY
The system is performing another task 
with a higher priority.
Wait a few moments for the system to complete 
the task. If the message displays for a long 
period of time, the processor could be locked 
up.
TRANSMIT FAIL
The panel has attempted to 
communicate with the central station 
10 times and has not succeeded.
Verify your communication type, account 
number, and IP address.
ENTER CODE (When 
entering Programming)
A lockout code has been programmed 
for the panel.
Enter the lockout code.
Listed Compliance Specifications
37.1 Introduction
The programming and installation specifications contained in this section must be completed when installing 
the XTLplus in accordance with any of the ANSI/UL or SIA burglary standards. Additional specifications may 
be required by a particular standard.
37.2  Use Marking
Commercial Central Station, Household Burglar Control Unit.
37.2  Locations and Wiring
Locations and wiring methods shall be in accordance with the National Electrical Code, ANSI/NFPA 70 and the 
Standard for Installation and Classification of Burglar and Holdup Alarm Systems, UL 681.
37.3  NFPA 72
This equipment should be installed in accordance with Chapter 29 of the National Fire Alarm Code,  
ANSI/NFPA 72, (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269). Printed 
information describing proper installation, operation, testing, maintenance, evacuation planning, and repair 
service is to be provided with this equipment. Warning: Owner’s instruction notice, not to be removed by 
anyone except occupant.
37.4  Types Of Service
Suitable for Central Station Burglar. Suitable for Household Fire and Household Burglar. Test weekly. The 
XTLplus has not been evaluated by Intertek for Household Fire.
37.5  Police Station Phone Numbers
The XTLplus must not be programmed to communicate with a police station.
37.6  Bypass Reports
The bypass reports must be programmed as YES for all listed burglary applications.
37.7  System Testing
The system must be tested once per week and Checked by a qualified technician once every three (3) years.
COMPLIANCE