False Alarm Reduction Programmable Options
ANSI/SIA CP-01-2010
41.1 Shipping Defaults and Recommended Programming
SIA CP-01 FEATURE
PARAGRAPH # AND
DESCRIPTION
DMP PROGRAMMING
GUIDE LT-1434
SECTION #
REQUIREMENT
RANGE
SHIPPING
DEFAULT
RECOMMENDED
PROGRAMMING*
4.2.2.1 Exit Time
28.6 Exit Delay
Required
(Programmable)
45 sec. - 250 sec.
60
Seconds
60 Seconds
4.2.2.2 Progress
Annunciation
33.14 Prewarn
Address
Allowed
Individual keypads may
be disabled per zone
All
keypads
enabled
All keypads enabled
4.2.2.3 Exit Time Restart 28.6 Exit Delay
Required Option
For re-entry during exit
time
Enabled
Enabled
4.2.2.5 Auto Stay Arm on
Unvacated Premises
28.17 Occupied
Premise - See Install
Guide
Required Option
(except for remote
arming)
Occupied Premise NO/
YES option
Enabled
Enabled Yes
for Residential
Applications
4.2.4.4 Exit Time and
Progress Annunciation/
Disable - for Remote Arm
Not Available on
Remote Arming
Allowed Option
Progress Annunciation
Always disabled for
Remote Arming
Not
Available
Remote Arming not
allowed for CP-01
installations.
4.2.3.1 Entry Delay(s)
28.5 Entry Delay
Required
(Programmable) Only
use Entry Delay 1. Do
not use Entry Delay 2.
30 sec. – 240 Sec.
**
30
Seconds
At least 30
Seconds
**
4.2.5.1 Abort Window –
for Non-Fire Zones
36.2 Transmit Delay
Required Option
Disable by zone or zone
type
Enabled
NT DY EX
Zone
Enabled
4.2.5.1 Abort Window
Time – for Non-Fire
Zones
36.2 Transmit Delay
Required
(Programmable)
20 sec., 30 sec., or
40 sec.
**
30
Seconds
At least 20
Seconds
**
4.2.5.1.2 Abort
Annunciation
36.2 Transmit Delay
Required Option
Annunciate that no
alarm was transmitted Yes
Yes
4.2.5.4.1 Cancel
Annunciation
Always Enabled - Not
Programmable
Required Option
Annunciate that a
Cancel was transmitted
(S49)
Always
Enabled
Yes
4.2.6.1 & 4.2.6.2 Duress
Feature
User Code + 1 =
Ambush Code Not
Available
Allowed Option
No 1 + derivative of
another user code/no
duplicates with other
user codes
Code +1
Always
Disabled
Not Programmable
4.3.1 Cross Zoning
33.16 Cross Zone
Required Option
Yes/No Zone
Programming
No
Enabled using
two or more
programmed zones
4.3.1 Programmable
Cross Zoning Time
28.7 Cross Zone Time Allowed
4 sec. - 250 sec.
0 Seconds Per walk path in
protected premises
4.3.2 Swinger Shutdown Not Available —
Always On
Required
1-6 trips
2 trips
2 trips
4.3.2 Swinger Shutdown
Disable
33.13 Swinger Bypass Allowed
For non-police response
zones
Yes
Enabled (all zones)
4.3.3 Fire Alarm
Verification
33.5 Zone Type
Required Option
FV Type Zone
No
Yes as required
(unless sensors can
self verify)
4.6.3 System Test
36.5 Walk Test
Allowed
Test all protection
devices
N/A
N/A
4.6.5 Communications
36.5 Walk Test
Not Allowed
N/A
N/A
N/A
* Programming at installation may be subordinate to other listed requirements for the intended application.
** For listed Installations, combined Entry Delay and Transmit Delay should not exceed 1 minute.
Local Bell
All non-fire zones such as Night, Day, Exit, Aux 1 and Aux 2 must be programmed for local bell enabled with a bell
cutoff time set to a minimum of 6 minutes to provide a cancel window of 5 minutes or greater. This does not apply
to manually operated zone types such as Panic and Emergency.
The requirements are superseded by any requirements for Commercial Burglar, Household Fire Warning, or
Household Burglar applications.
Minimum Installation Requirements: SIA CP-01-2010 minimum system installation requirements include an XTLplus,
Minimum Installation Requirements: SIA CP-01-2010 minimum system installation requirements include an XTLplus,
an 1135 Wireless Siren, a 9000 Series Wireless keypad, and communication to an SCS-1R receiver.