XTLplus Installation and Programming Guide
48
COMPLIANCE
Household Fire Warning System 
ANSI/UL 985 NFPA 72 Specifications
40.1  Bell Output Definition
The bell output of the Model XTLplus must be programmed to operate steady on burglary alarms and 
temporal on fire alarms. 
40.2  Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
40.3  Wireless Supervision Time
The Zone Information Supervision Time must be 3 minutes for fire devices.
40.4  Wireless Fire Verification
When used, the Model 1161 and 1162 wireless smoke detectors must not be programmed as Fire Verification 
(FV) zone type. 
40.5  Battery Standby
For listed applications, the panel must have 24 Hour battery standby operation. The Model XTL+BAT3500 
battery should be used for fire installations.
40.6  Test Frequency
The Test Frequency option must be programmed to send a report at least once every 30 days.