UTC Fire & Security Americas Corporation Inc 569E-LMRISE User Manual

Page of 3
2  
Learn Mode Rate of Rise Heat Sensors Installation Instructions 
• 
Do not mount the sensor close to devices that change 
temperature rapidly, such as ovens, heat vents, furnaces, 
or boilers. 
Equipment needed 
You will need the following equipment to install the sensors: 
• 
Phillips and flathead screwdrivers 
• 
Appropriate learn mode control panel documentation (for 
programming information) 
Programming 
The panel must learn (program) the sensor ID code in order to 
respond to sensor signals. For complete programming 
information, refer to the specific control panel documentation. 
To add the sensor to panel memory, do the following: 
1.  Separate the sensor from the base by twisting the sensor 
counter-clockwise and pulling the sensor off the base. Set 
the base aside. 
2.  Place the panel in program mode. 
3.  Proceed to the Learn Sensors menu. When the panel 
prompts you for a sensor group number, enter the group 
number (26). 
4.  Select the desired sensor number. 
5.  When the panel prompts you to trip the sensor, press and 
hold the learn switch on the sensor (
) until the 
panel beeps, indicating successful programming. 
Figure 2. Learn switch 
 
6.  Exit program mode. 
Testing 
Before permanently securing the sensor to the wall or ceiling, 
test the sensor from the installation location using one of the 
following methods. 
Caution: 
The test method described only tests rate-of-rise 
operation. These sensors cannot be field tested for their fixed 
temperature ratings without being destroyed. When used with 
care, the heat from a portable hair dryer (method 2) can be 
used for testing. Do not aim the hair dryer directly at the round 
disc on the sensor as this can cause it to pop off. If this 
happened, the sensor must be replaced. 
Method 1 
To test the sensor, do the following: 
1.  Place the panel in sensor test mode. 
2.  Rub your hands together vigorously, until they feel hot. 
3.  Place the palm of one hand on the round disc of the 
sensor, for about 7 to 10 seconds. 
4.  Listen for the appropriate number of beeps from interior 
sirens and speakers (refer to the specific panel 
documentation). 
5.  Exit sensor test mode. 
The sensor should reset in less than one minute. 
Method 2 
To test the sensor, do the following: 
1.  Place the panel in sensor test mode. 
2.  Plug in a portable hair dryer. 
3.  Hold the hair dryer about 12 to 18 in. away from the 
sensor, aiming it at the side of the sensor. 
4.  Listen for the appropriate number of beeps from interior 
sirens and speakers (refer to the specific panel 
documentation). 
5.  Exit sensor test mode. 
The sensor should reset in less than one minute. 
Mounting the sensor 
To secure the sensor to its permanent location, do the 
following: 
1.  Locate the base mounting holes (inner pair and outer pair) 
and mount the base to the wall or ceiling with the 
appropriate hardware (
). 
2.  Attach the sensor to the base.