Learn Mode Commercial Rate-of-Rise Heat Sensors Installation Instructions
Programming
The panel must learn the sensor ID code in order to respond to sensor signals. For complete 
programming information, refer to the specific panel installation instructions.
You must be free of static electricity before handling circuit boards. Wear a 
grounding strap or touch a grounded, bare metal surface to discharge static 
electricity.
Static
1. Separate the sensor from the base by twisting the sensor 
counter-clockwise and pulling it off the base. Set the 
base aside.
2. Place the panel in program mode.
3. Proceed to the LEARN SENSORS menu.
4. When the panel prompts you for a sensor group number, 
enter the fire group number (26).
5. Select the desired sensor number.
6. When the panel prompts you to trip the sensor, press and 
release the tamper switch on the sensor (Figure 1). Sys-
tem sirens beep indicating successful programming.
7. Exit program mode.
Figure 1. Tamper Switch Location
Testing
Before permanently securing the sensor to the wall or ceiling, test the sensor from the area it 
will be located, using one of the two methods below.
The test methods described below only test rate-of-rise detection. These sensors 
cannot be field-tested for their fixed temperature limits (135°F and 200°F) without 
being destroyed. When used with care, the heat from a portable hair dryer 
(Method 2) can be used for testing. Do not aim the hair dryer directly at the round 
disc on the sensor as this can cause it to pop off. If this happens, the sensor must be 
replaced.
¾
Method 1:
1. Place the panel in the sensor test mode.
2. Rub your hands together vigorously, until they feel hot.
3. Place the palm of one hand on the round disc of the sensor, for about 7 to 10 seconds.
4. Listen for the appropriate number of beeps from interior sirens and speakers (refer to the 
specific panel installation instructions).
5. Exit sensor test.
The sensor should reset in less than 1 minute.
¾
Method 2:
1. Plug in a portable hair dryer.
2. Hold the hair dryer about 12 to 18 inches away from the sensor, aiming it at the side of 
the sensor.
3. Listen for the appropriate number of beeps from interior sirens and speakers (refer to the 
specific panel installation instructions).
4. Exit sensor test.
The sensor should reset in less than 1 minute.
+
Tamper 
Switch
Caution
!