Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
 
GENERAL DATA 
2-22
 
 
2.2.12.  WALL TYPE (RAC-50WPA/60WPA/70WPA) 
OUTDOOR 
UNIT 
RAC-50WPA 
RAC-60WPA 
RAC-70WPA 
Minimum / Maximum indoor units 
connectable 
 
Minimum / Maximum connected 
capacity 
  
Nominal Cooling capacity (min - max) 
kW 
5.0(0.9-5.2) 
6.10 (0.9-6.5) 
7.00 (1.5-8.00) 
Nominal Heating capacity (min - max) 
kW 
6.00 (0.9-8.1) 
6.80 (0.9-8.5) 
8.00 (1.5-9.2) 
Nominal cooling power input (min - 
max) 
kW 
1.56 (0.155-1.900) 
1.85 (0.155-2.300) 
2.17 (0.200-2.820) 
Nominal heating power input (min - 
max) 
kW 
1.66(0.155-2.010) 
1.88 (0.120-2.550) 
2.2 (0.200-2.970) 
EER / COP 
 
3.21/3.61 
3.30 /3.62 
3.23/3.64 
SEER / SCOP 
 
6.1/4.3 
6.0/4.0 
6.8/4.4 
Energy class (SEER/SCOP)   
 
A+/A+ 
A+/A+ 
A+/A+ 
Noise level cooling (sound pressure)   
dB(A) 
50 
50 
52 
Noise level heating (sound pressure)   
dB(A) 
52 
53 
54 
Noise level (sound power) 
dB(A) 
65 
66 
67.0 
Air flow (Cooling / Heating)   
m
3
/h 
2160/2160 
2160/2160 
2820/2820 
Static pressure (nominal conditions, 
maximum) 
Pa 
Dimensions (H x W x D) 
mm 
650x850x298 
650x850x298 
800x850x298 
Weight 
kg 
45.0 
45.0 
55.0 
Colour (Munsell Code) 
 
Beige (5Y 7/2) 
Power supply 
 
220-230V , 1Ph , 50Hz  220-230V , 1Ph , 50Hz  220-230V , 1Ph , 50Hz 
Recommended fuse size 
16 
20 
30 
Starting current 
10.0 
8.5 
10.0 
Running current 
7.15-6.56/7.60-7.00 
8.50-7.80/8.60-7.90 
9.95~9.10 / 10.10~9.30 
Cable section  
mm
2
 
Ø2.0 
2.500 
2.500 
Interconnection between indoor unit 
and outdoor unit 
mm
2
 
Ø1.6 OR Ø2.0 
2x2.5 + 2x1.6 or 2.0 
2x2.5 + 2x1.6 or 2.0 
Piping diameter (Liq / Gas) 
  
1/4" / 1/2" 
1/4" / 1/2" 
1/4" / 5/8" 
Minimum piping length 
3.0 
3.0 
3.0 
Maximum piping length / height 
difference 
20 / 10 
30 / 20 
30 / 20 
Current quantity of refrigerant / 
Chargeless  
kg 
1.65 
1.65 
1.85 
Chargeless / Additional refrigerant 
charge 
m / g/m 
8/10 
30 / chargeless 
30 / chargeless 
Working range (cooling / heating) 
°C 
-10 ~ 43 / -15 ~ 21 
-10 ~ 43 / -15 ~ 21 
-10 ~ 43 / -15 ~ 21 
Refrigerant 
 
R410A 
R410A 
R410A 
Condenser Fan 
 
Propeller Fan 
Compressor 
Type 
 
2-Cylinder Rotary 
2-Cylinder Rotary 
2-Cylinder Rotary 
Oil Type 
 
HAF68D1
 
HAF68D1
 
HAF68D1
 
Oil Charge 
ml 
480 
480 
580 
Coil Resistance 
 
1.767 at 20
1.298 at 20
1.298 at 20
2.1649 at 75
1.767 at 75
1.767 at 75
Quantity 
 
NOTE: 
1.  The Sound Pressure Level is based on the following conditions:  
1 meter from the unit front surface and 1 meter from floor level  
The above data was measured in an anechoic chamber. Please take into consideration reflected sound of your specific 
site