Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
GENERAL DATA 
 
2-25 
 
2.2.15.  FLOOR TYPE (RAF-25PXA/35PXA/50PXA) 
 
INDOOR 
Unit 
RAF-25PXA 
RAF-35PXA 
RAF-50PXA 
Nominal capacity adjustable  
  
Nominal Cooling capacity (min - max) 
kW 
2.5(0.9-3.1) 
3.5(0.9-4.0) 
5.0 (0.9-5.2) 
Cooling sensible capacity  
kW 
2.50 
2.95 
3.80 
Nominal Heating capacity (min - max) 
kW 
3.4(0.9-4.4) 
4.5(0.9-5.0) 
6.5 (0.9-8.1) 
Noise level cooling (sound pressure) 
(SL / L / M / H) 
dB(A) 
20/26/31/38 
20/26/31/39 
22/29/36/43 
Noise level heating (sound pressure) 
(SL / L / M / H) 
dB(A) 
20/26/31/38 
20/26/31/39 
22/29/36/44 
Noise level (sound power) 
dB(A) 
55 
56 
59 
Air flow cooling mode (SL / L / M / H) 
m
3
/h 
270/390/510/630 
270/390/510/630 
300/450/540/720 
Air flow heating mode (SL / L / M / H)  
m
3
/h 
300/420/540/660 
300/420/540/660 
330/480/570/750 
Fan Motor 
25 
25 
25 
Drain pump pressure lift 
cm 
Static pressure (SL / L / M / H) 
(nominal conditions SP 00) 
Pa 
Dehumidification 
l/h 
1.4 
1.9 
2.8 
Included drain pump 
 
no 
no 
no 
Max. height available for drain pump 
(RAD/RAI only) 
 
no 
no 
no 
Dimensions (H x W x D) 
mm 
590x750x215 
590x750x215 
590x750x215 
Panel dimensions (H x W x D) 
mm 
Weight 
kg 
15.0 
15.0 
15.0 
Colour (Munsell Code) 
 
Pearl White 
Condensate Drain 
mm 
φ16 
φ16
 
φ16
 
Panel weight 
kg 
Panel reference 
 
Color of the panel (RAL) 
 
Running current 
2.66-2.55/3.63-3.47 
4.68-4.48/5.60-5.36 
7.16-6.85/8.17-7.82 
Power supply 
 
36 V DC from outdoor 
unit 
37 V DC from outdoor 
unit 
38 V DC from outdoor 
unit 
Cable section 
mm² 
1.250 
1.250 
1.250 
Piping diameter (Liq / Gas) 
  
1/4" / 3/8" 
1/4" / 3/8" 
1/4" / 1/2" 
Drain diameter (ext) 
mm 
φ16 
φ16 
φ16 
Remote control (standard/optional)  * 
 
RAR-5E4/ SPX-RCDB 
RAR-5E4/ SPX-RCDB
 
RAR-5E4/ SPX-RCDB
 
Filter 
 
 
 
 
ACL Filter 
 
Nano Titanium 
Nano Titanium 
Nano Titanium 
Dimensions (H x W x D) 
mm 
48x243x8 
48x243x8 
48x243x8 
Pre-filter (Standard / Optional) 
 
Nano Stainless/- 
Nano Stainless/- 
Nano Stainless/- 
*
more information regarding remote control can be found in Chapter 9
*
 
 
NOTE: 
1.  The nominal cooling and heating capacity is the 
combined capacity of the HITACHI standard split 
system, and are based on the ISO 5151.
 
 
2.  The Sound Pressure Level is based on the following 
conditions:  
1.5  meter beneath the Unit 
The above data was measured in an anechoic 
chamber. Please take into consideration reflected 
sound of your specific site
 
 
Operation Conditions 
Cooling 
Heating 
 
Indoor Air Inlet Temperature
 
dB 
27.0 °C
 
20.0 °C 
 
WB 
19.0 °C
 
 
 
Outdoor Air Inlet 
Temperature
 
dB 
35.0 °C
 
7.0 °C
 
 
WB 
 
6.0 °C 
 
Piping Length: 5.0 meters; Piping Lift: 0 meter 
dB: Dry Bulb; WB: Wet Bulb