Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
 
14-22
 
 
LD303 lit, normal cooling or heating mode 
operation.
LD301 blinking, LD303 lit, unit in full load 
condition. (Not malfunction)
LD301 only blinking, check blink error code as 
below.
Replace outdoor PWB 
Main. (Communication 
circuit abnormal) 
Repair the abnormal 
portion.
Operate the unit by remote 
control or by pushing the 
test/service switch button.
Specify the abnormal portion.
Refer above LED 9 times blink.
Is AC220~240V being 
supplied to terminal L and N?
Check power supply.
Is DC220~320V being generate? (Measure point 
shall refer to label on top of electrical cover)
Replace outdoor 
P.W.Bs. (Voltage rectify 
circuit abnormal)
Replace outdoor 
P.W.Bs. (Voltage sensor 
circuit abnormal)
Check if thermistor connector mis or 
half insert.
Re-connect the 
thermistor.
Check if thermistor wire disconnector 
or short.
Replace outdoor PWB  
main . (Thermistor sensor 
circuit abnormal) 
Compressor 
temperature rise 
check by OH 
thermistor.
Re-connect OH 
thermistor.
Check if OH thermistor wire 
short.
Replace outdoor P.W.Bs 
if still cannot fix after 
review the cycle.
Review the cooling cycle.
No
Yes
Compressor 
stop
Electrical 
assembly 
abnormal
Abnormal other than electrical assembly
Below AC170 or 
more than AC240V
Yes
Yes
Abnormal
AC170~230V
No
Normal
Abnormal
Yes
Abnormal
Yes
LD301  1 time  blinking.
Reset stop
Confirm blinking times of LD301
Compressor start
LD301  9 times  blinking.
Communication error
LD301  10 times  blinking.
Supplied voltage error
Normal
LD301  7 times  blinking.
Thermistor abnormal
No
Change thermistor.
Normal
OH thermistor temperature 
rise
LD301  6 times  blinking
No
Check if OH 
thermistor 
connector mis 
or half insert.
Abnormal
Normal
Change OH 
thermistor.
Abnormal
Overload lower limit cut
LD301  5 times  blinking
Compressor 
load heavy 
causing 
operation 
stop.
Cooling: Is the outdoor unit 
heat exchanger pipe choke or 
condenser block by 
something?
Heating: Is the indoor unit 
heat exchanger pipe choke or 
filter block by dust?
Countermeasure 
the cause of the 
problem.
Check the 
abnormal 
portion.
Is there any abnormality to the cooling cycle.
Yes
Yes
No
Yes
No