GENERAL DATA
2-28
2.2.18. FLOOR TYPE (RAC-25FPA/35FPA/50FPA)
OUTDOOR
UNIT
RAC-25FPA
RAC-35FPA
RAC-50FPA
Minimum / Maximum indoor units
connectable
connectable
-
-
-
Minimum / Maximum connected
capacity
capacity
-
-
-
Nominal Cooling capacity (min - max)
kW
2.50 (0.90 - 3.10)
3.50 (1.10 - 4.20)
5.00 (1.90 - 5.20)
Nominal Heating capacity (min - max)
kW
3.40 (0.90 - 4.40)
4.20 (1.10 - 5.20)
6.00 (2.20 - 7.30)
Nominal cooling power input (min -
max)
max)
kW
0.67 (0.25 - 1.29)
0.94 (0.25 - 1.40)
1.51 (0.50 - 2.10)
Nominal heating power input (min -
max)
max)
kW
0.85 (0.25 - 1.25)
1.05 (0.25 - 1.80)
1.66 (0.50 - 2.70)
EER / COP
3.73/4.00
3.72 / 4.00
3.31 / 3.61
SEER / SCOP
5.8/4.3
6.0/4.3
5.9/4.0
Energy class (SEER/SCOP)
A+/A+
A+/A+
A+/A+
Noise level cooling (sound pressure)
dB(A)
47
48
51
Noise level heating (sound pressure)
dB(A)
49
49
52
Noise level (sound power)
dB(A)
61
62
65
Air flow (Cooling / Heating)
m
3
/h
1860 / 1620
1920 / 1620
2160 / 2160
Static pressure (nominal conditions,
maximum)
maximum)
Pa
-
-
-
Dimensions (H x W x D)
mm
548x750x288
548x750x288
600x792x299
Weight
kg
31.0
35.0
40.0
Colour (Munsell Code)
T-Beige (ZYY95)
Power supply
230V / 1Ph / 50Hz
230V / 1Ph / 50Hz
230V / 1Ph / 50Hz
Recommended fuse size
A
15
15
25
Starting current
A
3.43/4.11
4.30/4.81
6.63/7.29
Running current
A
3.43/4.11
4.30/4.81
6.63/7.29
Cable section
mm
2
3x1.50
3x1.50
3x2.50
Interconnection between indoor unit
and outdoor unit
and outdoor unit
mm
2
2x0.75
2x0.75
2x0.75
Piping diameter (Liq / Gas)
1/4” - 3/8”
1/4” - 3/8”
1/4” - 1/2”
Minimum piping length
m
5.0
5.0
5.0
Maximum piping length / height
difference
difference
m
20 / 10
20 / 10
20 / 10
Current quantity of refrigerant /
Chargeless
Chargeless
kg
0.87
1.05
1.25
Chargeless / Additional refrigerant
charge
charge
m / g/m
20/-
20/-
20/-
Working range (cooling / heating)
°C
-10~43/-15
~
21
-10~43/-15~21
-10~43/-15~21
Refrigerant
R410A
R410A
R410A
Condenser Fan
Propeller Fan
Compressor
Type
ROTARY
ROTARY
ROTARY
Oil Type
FV50S
FV50S
HAF68DIU
Oil Charge
ml
320
320
440±20
Coil Resistance
0.875 at 25
C
0.875 at 25
C
1.65 at 25
C
1.043 at 75
C
1.043 at 75
C
Quantity
1
1
1
NOTE:
1. The Sound Pressure Level is based on the following conditions:
-
1 meter from the unit front surface and 1 meter from floor level
The above data was measured in an anechoic chamber. Please take into consideration reflected sound of your
specific site
specific site