Rotation field direction
Check the direction of the voltage rotation field on the 
measured value display of the UMG 96RM-M. 
Usually there is a "clockwise" spinning rotation field.
Checking the phase assignment
The assignment of the phase conductor to the current 
transformer is correct if a current transformer is short 
circuited at the secondary terminals and the current 
shown by the UMG 96RM-M in the corresponding phase 
sinks to 0A.
Checking the power measurement
Short circuit all current transformer outputs except for 
one and check the displayed power.
The UMG 96RM-M must only show one rating in the 
phase with the non-short-circuited current transformer 
input. If this does not apply, check the measured voltage 
connection and the measured current connection.
If the magnitude of the real power is correct but the sign 
of the real power is negative, this can be due to two 
causes:
•  The connections S1 (k) and S2 (I) on the current 
transformer are inverted.
•  Active energy is being returned to the network.
Checking the measurement
If all voltage and current measurement inputs are 
correctly connected, the individual and sum power 
ratings are accurately calculated and displayed. 
Checking the individual power ratings
If the current transformer is assigned to the wrong 
phase conductor, the associated power rating will be 
incorrectly measured and displayed. 
The assignment of the phase conductor to the current 
transformer on the UMG 96RM-M is correct if there 
is no voltage between the phase conductor and the 
associated current transformer (primary).
In order to ensure that a phase conductor on the voltage 
measurement input is assigned to the correct current 
transformer, the respective current transformer can be 
short-circuited at the secondary terminals. The apparent 
power shown by the UMG 96RM-M must then be zero 
in this phase.
If the apparent power is correctly displayed but the real 
power is shown with a "-" sign, the current transformer 
terminals are inverted or power is being fed to the power 
company.