UMG 96RM-M
M-Bus interface
The data of the parameter list and measurement values 
list can be accessed via the M-Bus interface with the 
help of the primary or secondary address. Changing 
these values is not possible via the M-Bus.
The primary device address is factory preset to „1“. 
The extended section of the 8-Byte long secondary 
address is factory preset to contain the device serial 
number and can be individually changed via the corre-
sponding parameters. The device-specific section of the 
secondary address cannot be adjusted (see page 42).
M-Bus device features
•  Addressing possible via primary address and sec-
ondary address (0 .. 250)
•  Freely selectable number of data points (0 .. 27)
•  Supports protocol types:  
SND_NKE/$E5 and REQ_UD2/RSP_UD2
•  Slave search: Search on M-Bus
C
The UMG 96RM-M loads the M-Bus with 
an M-Bus device load of 1.5 mA.
Number of data points 
The number of data points to be transmitted for the 
RSP_UD2 telegram is defined via this address.
Address:  
080
Meaning:  
Number of data points for RSP_UD2
Setting range:   0 .. 27
Default setting:  0 (0 = All data points)
In order to call up all data points (0), a telegram must 
be sent.
Example: Read out data points 1 to 6
Set the parameter of the address to 6. With each request 
all data points up to and including data point 6 will be 
transmitted.
Example: Read only data point 10
Set the parameter of the address to 10. With each re-
quest all data points up to and including data point 10 
will be transmitted. Use only the data point required and 
ignore those that are not required.