Where more than one parameter is associated with the output relay, and when the output relay is
triggered by more than one measure, switch-off will be realized by the last remaining measure.
A pulse has been
generated from
3.Pulse A Output
Device has 2 Pulse Outputs. It is possible to see, which one of these outputs generate pulse, from the LCD at
any time.
Each time the consumed energy increases by an increment of “Prm”, a pulse, as long as the “Dur” value entered
(msec), is produced in the Pulse Outputs.
A pulse has been
generated from
4.Pulse R Output
4.7   Pulse Outputs (3. Pulse  A / 4. Pulse R) (MPR63
-23/43
)
Energy
t (msec)
Prm
3.Pulse A / 4.Pulse R
t (msec)
5-24V
max 30V
Dur
(Duration)
Figure 30: 
Energy - Pulse output graphic
Dly1 (Delay time for the 1st parameter)
When the triggering signal is sent to the relay1, the relay1 will wait during the delay time before  switching on.
If the alarm signal is over during the delay time, the relay1 will not switch on.
Figure 29: 
Setting the delay time for the 1st parameter.
Warning :
You may quit all settings any time by           key.
You must record any change in the settings by         menu key.
OR
GATE
Dly
Time
Hys.
Output
Relay
Pr1
Pr2
Pr3
Hold
Reg.
Digital Output Control