Entes MPR-63 Mains-analysis device, Mains analyser MPR-63 User Manual

Product codes
MPR-63
Page of 47
24
Figure 25: 
Setting of I
L
1
 as the first parameter with 1.5 A < I
L1
 < 2.5 A having 20 mA hysterisis and
                 10 seconds delay time.
Pr1 (1st Parameter)
Example of programming parameter:
Here, the steps of setting of I
L
1
 as the first parameter (Pr1)
with 1.5 A < I
L1
 < 2.5 A having 20 mA hysterisis and 10 seconds
delay time will be described. 
See Figure 25
.
The following Pr2 and Pr3 follow the same procedure.
It is advised to keep unused parameters in “Off” mode to
prevent false alarms.
If any parameter will not be associated with Pr1, “Off”
option must be selected.