Hi1 (High / over value for the 1st parameter)
When the measured value is over the Hi1 value, Relay 1 (or Relay 2) is switched on complying with Hs1
(Hysterisis 1) and Dly1 (Delay 1) values.
Lo1 (Low / under value for the 1st parameter)
When the measured value is under the Lo1 value, Relay 1 (or Relay 2) is switched on complying with Hs1
(Hysterisis 1) and Dly1 (Delay 1) values.
Figure 27: 
Setting the low (under) value for the 1st parameter
Figure 26: 
Setting the high (over) value for the 1st parameter
Hs1 (Hysteresis value for the 1st parameter)
This function is added to prevent system from unexpected oscillations during switch off.
When the switch off values of the associated  parameters are over (or under) of Lo1 (or Hi1) values as the hysterisis
value respectively, the Relay1 switches off.
Figure 28: 
Setting the hysteresis value for the 1st parameter
Warning :
You may quit all settings any time by           key.
You must record any change in the settings by         menu key.