Tripp Lite 2.9kW Single-Phase ATS / Metered PDU, 120V Outlets (24 5-15/20R, 1 L5-30R), 2 L5-30P, 2 10ft Cords, 2U Rack-Mount PDUMH30AT Data Sheet

Product codes
PDUMH30AT
Page of 4
ATS configurations enable fault-tolerant, hot-swappable UPS protection when used with a single UPS and fully redundant UPS protection when each cord
is connected to a separate UPS system (in a two-UPS environment, the primary input cable must be supported by an online UPS with zero transfer time
similar to Tripp Lite SmartOnline series)
Advanced ATS configurations utilizing separate mains circuits, backup generators and even separate out of phase utility power grid feeds are fully
supported
On-board ATS processor constantly evaluates power quality on both inputs to prevent transfer to the secondary source when unavailable or of lower
quality than the primary source
Front panel LEDs confirm power availability on both input lines
 TAA Compliant Version Available - Order Tripp Lite PDUMH30ATAA 
Specifications
General Info
RoHS
Y
OVERVIEW
Style
Rackmount
PDU Type
Auto-Transfer Switch; Metered
OUTPUT
Output Capacity Details
2.88kW (120V), 3.05kW (127V), 2.4kW (100V); 30A maximum (agency de-rated to 24A continuous)
Frequency Compatibility
60 Hz
Output Receptacles
(24) 5-15/20R; (1) L5-30R
Output Nominal Voltage
100-127V nominal, single phase
Overload Protection
2 20A output breakers protect 12 5-15/20R outlets each
Outlet Type
5-15/20R, L5-30R
INPUT
PDU Input Voltage
100; 120; 127
Recommended Electrical Service
30A 120V
Maximum Input Amps
30
Maximum Input Amps Details
Agency de-rated to 24A continuous
PDU Plug Type
NEMA L5-30P
Input Cord Length (ft.)
10
Input Cord Length (m)
3
Input Cord Details
Two input power cords enable connection to separate Primary and Secondary input power sources
Input Phase
Single-Phase