D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN
EN | 28
Bosch Security Systems | 1/04 | 47775E
 
9 (such as 9, 19, 29, 39, and so on): The AC
Fail Time interval is in minutes and an AC Fail
Event is transmitted after the loss of AC for this
amount of time.
An additional AC Fail Event is transmitted after
12 hours if the AC Fail condition is still present.
 
0 (such as 10, 20, 30, and so on): The AC Fail
Time interval is in seconds and an AC Fail
Event is transmitted after the loss of AC for this
amount of time.
An additional AC Fail Event is transmitted after
12 hours if the AC Fail condition is still present.
For the following items to be true, 
AC Fail/Res Rpt
must be programmed as No and 
AC Tag Along
must also be programmed as No.
When you program 
AC Fail Time
, if the second
digit is:
 
1, 3, or 5 (such as 3, 5, 11, 13, 15, 21, and so
on): The AC Fail Time interval is in minutes.
No AC Fail or AC Restoral Events are
transmitted.
 
2, 4, or 6 (such as 2, 4, 6, 12, 14, 16, 22, 24, 26,
and so on): The AC Fail Time interval is in
seconds. No AC Fail or AC Restoral Events are
transmitted.
 
7 (such as 7, 17, 27, 37, and so on): The AC
Fail Time interval is in minutes. An AC Fail
Event is only transmitted after 6 hours if the AC
Fail condition is still present.
 
8 (such as 8, 18, 28, 38, and so on): The AC
Fail Time interval is in seconds. An AC Fail
Event is only transmitted after 6 hours if the AC
Fail condition is still present.
 
9 (such as 9, 19, 29, 39, and so on): The AC
Fail Time interval is in minutes. An AC Fail
Event is only transmitted after 12 hours if the
AC Fail condition is still present.
 
0 (such as 10, 20, 30, and so on): The AC Fail
Time interval is in seconds. An AC Fail Event is
only transmitted after 12 hours if the AC Fail
condition is still present.
Firmware versions 6.20 and higher: To
eliminate AC Reporting, AC Tag Along
and AC Fail/Res Rpt must be
programmed No and the second digit of
the AC Fail Time must be a 1, 2, 3, 4, 5, or
6.
Firmware versions 6.10 and lower: To
eliminate AC Reporting, AC Tag Along
and AC Fail/Res Rpt must be
programmed No.
Firmware versions 6.10 and lower: To
eliminate AC Reporting, AC Tag Along
and AC Fail/Res Rpt must be
programmed No.
AC Fail/Res Rpt
Default:
No
Selection:
Yes or No
Yes
Send AC Fail and AC Restoral
Reports.
No
Does not send AC Fail and AC
Restoral Reports.
AC Power Supervision Reports are sent to the
central station and local printer at the time
programmed for 
AC Fail Time
.
0101
0101
0101
To comply with NFPA standards and UL
864 requirements for commercial fire
systems, program this item as No and
program AC Tag Along as Yes. AC
Restoral Reports are not transmitted.
AC Tag Along
Default:
Yes
Selection:
Yes or No
Yes
Send AC messages as tag along events.
No
Do not send AC messages as tag along
events.
Send AC Reports only if any other event occurs
while AC is off-normal.
If AC Tag Along is set to Yes and a
subsequent event is generated, the AC
Fail Event is transmitted first, prior to any
subsequent events transmitting.
0101
0101
0101
AC Tag Along is required for NFPA and
UL 864 commercial fire systems. Be sure
to program AC Fail/Res Rpt as No if AC
Tag Along
 is programmed Yes.