Bosch Appliances Home Security System D7412G User Manual

Page of 142
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN
EN | 29
Bosch Security Systems | 1/04 | 47775E
AC/Battery Buzz
Default:
No
Selection:
Yes or No
Yes
Initiates panel-wide trouble tone at all
command centers.
No
Does not initiate panel-wide trouble
tone at command centers
Initiate a panel-wide trouble tone at command
centers when AC fails or battery is low or missing.
This program item does not prevent the 
SERVC AC
FAIL
 or 
SERVC BATT LOW
 displays.
0101
0101
0101
To comply with NFPA standards and UL
864 requirements for commercial fire
systems, program this item as Yes.
De-selecting individual command centers
for panel-wide trouble tones: Panel-wide
trouble tones for programming the CC
Trouble Tone in the command center
parameters to No can turn off individual
command centers [based on their CC# (1
to 8)].
Bat Fail/Res Rpt
Default:
Yes
Selection:
Yes or No
Battery Failure and Restoral Reports are sent
to the central station. They are routed to the
telephone number programmed for
Power/Phone Events.
Modem
Reports
Missing or
shorted
Discharged
below 12.1 VDC
BATTERY
MISSING
BATTERY LOW
Yes
BFSK
Reports
Missing, shorted
low battery
TROUBLE
ZONE 9
No
Battery Failure and Restoral Reports are NOT
sent to the central station.
0101
0101
0101
To comply with NFPA standards and UL
864 requirements for commercial fire
systems, program this item as Yes.
2.6
Printer Parameters
Up to three D9131A Parallel Printer Interface
Modules can be connected to the D9412G’s (one
printer for the D7412G’s) SDI bus. Each printer is
identified by an address of 17, 18, or 19. Options are
available for Routing Reports and area assignments.
Printer Address
Default:
17
Selection:
17, 18, or 19 (only 17 is available for
the D7412G)
Enter the printer address you are programming.
P## Area Assign
Default:
1
Selection:
1 to 8
Assign an area to the printer programmed in 
Printer
Address
.
P## Supervised
Default:
No
Selection:
Yes or No
Yes
Only one printer can be installed for
this 
P## SDI
 address.
No
More than one unsupervised printer
can be installed using this 
P## SDI
address using the same address DIP
switch setting.
Supervise this SDI address and generate Trouble
SDI ## Reports and local trouble annunciation if a
problem occurs with this printer or the SDI bus.
Unsupervised printers sharing the same
address setting print the same text.
Trouble SDI ## Reports are always
reported as Area 1, Account 1 Events
regardless of where the SDI device is
assigned.