Bosch Appliances Video Game Controller d9412gv3 User Manual

Page of 154
D9412GV3/D7412GV3 | Program Entry Guide | 6.0  ACCESS CONTROL 
EN | 141 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
 
All SDI devices, regardless of area 
assigned, report to Area 1, Account 1 by 
default upon SDI failure. If a D9210B 
becomes disconnected, an SDI Fail ## 
and a Missing Point ### Event is 
created. 
 
 
If the D9210B is not programmed with a 
D# Entry Area, 9210 NOT READY 
appears at the keypad with this door 
assigned to it when you press the 
[ENTER] key.  
D#CC#Scope 
Default: 
Selection: 
0 to 8 
1 to 8 
Determines disarming rights. The 
user’s access level and the CC # 
Scope
 determines which areas are 
disarmed. 
Only the area assigned to the D# 
Entry Area
 disarms this door. 
Enter the keypad number (CC#) which determines 
the scope of the user ID’s disarming rights. Areas 
disarm on the basis of this keypad’s scope and the 
authority level of the user. 
 
The D# CC# Scope prompt is limited to 
the first 8 keypads. 
D# Custom Function 
Default: 
0 (Disabled) 
Selection: 
0, 128-143 (128-131 on the 
D7412GV3) 
Custom function disabled. 
128-143 
The custom function number that 
executes upon a valid ID, given the 
appropriate user access level and 
area arm state. 
You can program a custom function to run at the 
keypad programmed for CC# Scope. This custom 
function activates only for users with an L## 
Function Level?
 Assignment (refer to Section 2.10 
User Interface 
on page 76) in which a valid ID can 
execute a custom function during the armed or 
disarmed state. The user number to which the token 
is assigned must have an assigned passcode. 
If D# Disarm On Open is set to Yes for the same 
door, and L## Function Level? is set to D or C, the 
custom function executes when the door is physically 
opened. 
 
A user’s access level and the armed state 
of the area determine whether the custom 
function activates. This access level is 
programmed in the L## Function Level? 
prompt. Refer to 2.10 User Interface on 
page 59. 
Table 39 on page 141 shows how this programming 
affects custom function activation. 
 
Table 39: Effects of Programming on Custom 
Function Activation 
 
 
L## Function 
Level? 
Custom Function Activation 

(Armed) 
User token activates the custom 
function assigned to the Door 
Controller only while the entry area 
for the Door Controller is Master 
Armed or Perimeter Armed. 

(Disarmed) 
User token activates the custom 
function assigned to the Door 
Controller only while the entry area 
for the Door Controller is disarmed. 

(Armed and 
Disarmed) 
User token activates the custom 
function assigned to the Door 
Controller regardless of the armed 
state of the entry area. 

 
User token does not run the custom 
function assigned to the Door 
Controller. 
 
 
 
 
A user’s security level must have an M, 
P, or D to operate the custom function. 
D# Door Point 
Default: 
Selection: 
0 to 127, 129 to 247(0 to 75 on the 
D7412GV3) 
1 to 127, 
129 to 247 
The point number assigned to this 
door. Points 128 and 248 are 
reserved by the control panel for 
internal use. 
No point number is assigned to this 
door. 
Enter the point number assigned to this door. This 
point cannot be used for any other point 
assignments.