D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 62 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
View Memory 
Default: 
Selection:  -, E, or P 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
View Event 
Memory 
[COMMAND][4][0] 
Use this function to view prior alarm, trouble, and 
supervisory activity occurring since the last time the 
system armed. Event memory is not cleared until the 
area re-arms. 
View Point Status 
Default: 
Selection: 
-, E, or P 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
10 
View Point Status  (Menu function 
only) 
Use this function to view points assigned to the area 
where the keypad is assigned. This function shows 
point text and the electrical condition (normal, open, 
short, and missing) of each point in the area. 
Walk Test 
Default: 
Selection:  -, E, or P 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
11 Walk 
Test 
[COMMAND][4][4] 
Use this function to test Controlled points in areas 
within the keypad’s scope without sending reports to 
the central station. 24-hour points cannot be tested 
using this Walk Test Mode. 
Fire Test 
Default: 
Selection: 
-, E, or P 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
12 Fire 
Test 
[COMMAND][5][8] 
Use this function to test 24-hour points in areas within 
the scope of the keypad where the function is 
entered. Controlled points, P## Type 12, 3, cannot 
be tested using the Fire Walk Test Mode. 
Send Report 
Default: 
Selection: 
-, E, or P 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
13 Send 
Report 
[COMMAND][4][1] 
or 
[COMMAND][4][2] 
Use this function to test the communication link 
between the control panel and the central station 
receiver(s). It can send a Test Report or a Status 
Report to the phone numbers programmed in 
Routing. The Test Report includes additional 
information if Expand Test Report is enabled in  
Section 2.1 Phone on page 12. 
2.10.3 Access Control Functions 
Door Control 
Default: 
Selection:  -, E, or P 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
14 Door 
Control 
[COMMAND][4][6] 
#14 Door Control [COMMAND][4][6]) 
This top level display must be enabled for the user to 
access the cycle door, unlock door, and secure door 
functions (refer to Section 2.10.6 Authority Level 
Selections
 on page 66). Use this item when 
programming door control in your function menu. 
Access Ctl Level 
Default: 
Selection:  -, E, or P 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
37 
Access Control 
Levels 
(Menu function 
only) 
Shows the current on or off state of control levels 1 
through 14, pertaining to Access Control Only, (L## 
Access Level
 and L## Disarm Level). The user can 
toggle levels on and off and invalidate  access control 
levels during an extended period. This change only 
affects the user’s token or cards; it does not affect 
keypad Door Control functions.